BLD14-00681
| FIRE-Final Inspection | 8/5/2015 | 8/5/2015 | 8/5/2015 3:58:10 PM | P | PART |
|
|
Final fire life-safety inspection for apartment building. Tested some new exit signs added to clarify egress paths in some areas. Also retested some emerg. lights that were not working last visit. Tested last dry pipe fire sprinkler system, that failed last test. All fire sprinklers are fully tested, however some systems are still shutdown as some painted heads have to be changed out. The fire alarm system has been fully tested however, it is not being monitored off-site because of the fire sprinkler work being done. I have approved TCO for staff only personel to work in the leasing office only. I have not approved TCO for any use of the building for public use, access for residents, or for any overnight stays.
|
FIR14-00815
| INSP-Final Inspection | 8/5/2015 | 8/5/2015 | 8/5/2015 3:51:25 PM | P | PART |
|
|
Pre-final inspection for fire sprinkler systems. All systems have been fully tested and are operational. Left contractor with a punchlist of minor items (mostly escutcheons missing). Also some of the wet systems are still shut down as some painted heads need to be changed out. Will reshedule final inspection when all work is completed.
|
FIR14-00887
| INSP-Sprinkler Rough-in/Hydro | 8/4/2015 | 8/5/2015 | 8/5/2015 12:12:30 PM | A | PASS |
|
|
Hydrostatic test of FS U/G supply line from city connection to BOR stub up. 200 psi @ 2 hours - PASSED Also conducted flush test of this same supply line - flushed clear after 2 attempts. OK to connect to A/S BOR.
|
FIR14-00603
| INSP-Sprinkler Rough-in | 8/4/2015 | 8/5/2015 | 8/5/2015 12:09:49 PM | A | PASS |
|
|
Retest of dry pipe system #1 for the north side parking garage. PASSED - tripped within 58 seconds to waterflow.
|