Print Statement | | | 5/7/2020 | | DONE |
|
|
|
2nd notice
|
Print Statement | | | 4/13/2020 | | DONE |
|
|
|
1st statement
|
First Notice | 7/22/2019 | 7/22/2019 | 3/11/2020 | | DONE |
Brian Scoles
|
|
|
This permit finaled on the web by Nicholas Paige
|
Print Statement | | | 2/26/2020 | | DONE |
|
|
|
|
Final | 7/22/2019 | 7/22/2019 | 7/22/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- final ok- card signed
|
Final | 7/15/2019 | 7/17/2019 | 7/17/2019 | A | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- need air balance report on all hoods- need all equipment set into final place- need drip pans installed on north hood- need ss panel installed on deep fryer thats 18 inches higher open flame- went over with Dru, John and GC onsite- rest is good- temperature test pass above ceiling
|
Conference | 7/17/2019 | 7/17/2019 | 7/17/2019 | A | DONE |
Chad Schwendiman
|
|
|
11:00
|
Final | 7/10/2019 | 7/11/2019 | 7/11/2019 | P | PART |
Brian Scoles
|
|
|
partial final Phone #: ###-#### Inspection requested via web by Nicholas Paige- need to set up above ceiling temp test- need all appliances under class 1 hood set into place and flex gas piping hooked up- walked rest of job all good- few items for final
|
Final | 7/3/2019 | 7/8/2019 | 7/8/2019 | A | PART |
Brian Scoles
|
|
|
part final on gas and condensate Phone #: ###-#### Inspection requested via web by Nicholas Paige- need drip legs between shut off valves and appliances 4 locations on cook line- need to seal exterior penetration weather tight at gas meter location- need to reroute condensate drain on roof blocking door access to unit- went over with Ryan onsite about issues- need mech permit issued from company who installed 2 class 1 hoods and dishwasher hood talked to general contractor about this
|
Rough-in | 6/14/2019 | 6/14/2019 | 6/14/2019 | P | PASS |
Brian Scoles
|
|
|
please call dru prior to arriving Phone #: ###-#### Inspection requested via web by Nicholas Paige- R/I on area H1and H2 ok- ok for ceiling tiles- need to walk roof and all areas for fire damper labels on grid- will need to verify tempature test for above grid by final
|
Rough-in | 6/6/2019 | 6/7/2019 | 6/7/2019 | A | PART |
Brian Scoles
|
|
|
cover and fire damper Phone #: ###-#### Inspection requested via web by Nicholas Paige- area H1 and H2 fire damper angles and labeling on doors ok- grid 16 to grid 11 seal, registers and flex ok, ok for ceiling tiles
|
Rough-in | 6/3/2019 | 6/3/2019 | 6/3/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- area E to grid line 16 registers flex and labeling on fire damper doors ok- ok for ceiling tiles- still need labeling on grid all areas
|
Rough-in | 5/20/2019 | 5/21/2019 | 5/21/2019 | A | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- area 1 entry ok to cover registers and flex ok- area 3 mini split cassette ok to cover pending condensate hook up in area 3 entry- talked to Dru about this onsite
|
Rough-in | 5/14/2019 | 5/15/2019 | 5/15/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- area 2 C & D registers, seal and flex ok- ok for ceiling tiles
|
Rough-in | 5/7/2019 | 5/7/2019 | 5/7/2019 | P | PASS |
Chad Schwendiman
|
|
|
hardlid Phone #: ###-#### Inspection requested via web by Nicholas Paige - Okay to cover hard lids in rooms 431, 432, 433, 602, 603
|
Rough-in | 4/29/2019 | 4/30/2019 | 4/30/2019 | A | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- area E fire damper angles ok- area H1 and H2 seal on supply, return and exhaust ok excluding hard lid areas
|
Rough-in | 4/26/2019 | 4/29/2019 | 4/29/2019 | A | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- grease duct welds ok- all welds completed on grease duct system- seal area H1 supply duct only ok to insulate
|
Pressure Test | 4/26/2019 | 4/29/2019 | 4/29/2019 | A | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- 60lb gas pass whole system- still need to see low pressure test when piping installed to cook line and boilers
|
Rough-in | 4/23/2019 | 4/23/2019 | 4/23/2019 | P | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- Area 3G hard lids ok- Area 4 H1 and H2 fire damper framing ok- all grease duct fittings excluding drop tie ins to hood pass, need to see 4 more welds on transitions to hoods
|
Rough-in | 4/18/2019 | 4/18/2019 | 4/18/2019 | P | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- grease duct light test on 45 degree in ceiling 24x18 ok, 3 joints 24x18 with 20x10 and 20x10 tap ok, and 2 joints 20x10 with 90 degree ok- will see remaining weld after hood installed and welded- ok for first layer fire wrap from roof to 2nd 45 degree offset- access doors need installed
|
Rough-in | 4/15/2019 | 4/16/2019 | 4/16/2019 | P | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- area G seal on duct ok- ok to insulate- area E hard lids ok to sheetrock- walked roof
|
Rough-in | 4/11/2019 | 4/12/2019 | 4/12/2019 | A | PART |
Brian Scoles
|
|
|
Grease duct Phone #: ###-#### Inspection requested via web by Nicholas Paige- area A and B ok for ceiling tiles flex seal and registers ok- Area F seal on duct ok- area g above hard lid only seal ok- grease duct 1 joint at 45 degree south fitting ok- condensate to vestible NW side ok
|
Rough-in | 4/4/2019 | 4/5/2019 | 4/5/2019 | P | PART |
Brian Scoles
|
|
|
Grease Duct Phone #: ###-#### Inspection requested via web by Nicholas Paige- grease duct from roof down to 90 degree 2 pieces straight duct with 45 degree light test ok in ceiling- 2 pieces grease with 45 degree one end tested on floor light test ok-
|
Rough-in | 4/2/2019 | 4/3/2019 | 4/3/2019 | A | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- area 2 c and d hard lids ok to cover- area 2 c and d firedamper angles ok- ok for grid
|
Rough-in | 4/1/2019 | 4/1/2019 | 4/1/2019 | P | PART |
Brian Scoles
|
|
|
fire damper inspection Phone #: ###-#### Inspection requested via web by Nicholas Paige- area E fire damper clearances ok- ok for sheetrock and angles installed- area f no fire dampers
|
Rough-in | 3/29/2019 | 3/29/2019 | 3/29/2019 | P | PART |
Brian Scoles
|
|
|
Dru Phone #: ###-####- area E NW corner seal on all duct ok- ok to insulate- fire damper framing fail- went over condensate drain- Dru knows about fire damper framing issues- recall in when fixed
|
Override - Parcel Holds | 3/29/2019 | 1/1/1900 | 3/29/2019 | | |
|
|
|
this inspection is for mechanical- nothing to due with CSN hold
|
Rough-in | 3/19/2019 | 3/20/2019 | 3/20/2019 | A | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- area 2D seal on duct ok- ok for insulation- need to see framing complete in hard lid areas for exhaust drops
|
Rough-in | 3/11/2019 | 3/12/2019 | 3/12/2019 | A | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- area 1B hard lids ok- ok for sheetrock
|
Rough-in | 3/5/2019 | 3/6/2019 | 3/6/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige- area 1 A hard lids ok to cover- area 1 A&B fire damper angles ok- access doors will be put in after grid is in- ok for grid area 1 A&B only
|
Rough-in | 2/25/2019 | 2/26/2019 | 2/26/2019 | A | PART |
Brian Scoles
|
|
|
sealing and fire damper framing Phone #: ###-#### Inspection requested via web by Nicholas Paige- seal on duct area 2C only ok to insulate- fire damper framing area 2C only ok
|
Rough-in | 2/20/2019 | 2/21/2019 | 2/21/2019 | A | PART |
Brian Scoles
|
|
|
sealing and fire damper framing Phone #: ###-#### Inspection requested via web by Nicholas Paige- area 2 C/D need some framing on 3 dampers addressed- rest are good- recall in when seal and framing completed
|
Conference | 2/8/2019 | 2/12/2019 | 2/12/2019 | A | DONE |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Nicholas Paige
|
Conference | 1/31/2019 | 1/31/2019 | 1/31/2019 | A | DONE |
Chad Schwendiman
|
|
|
Discussed insulation requirements
|
Conference | 1/30/2019 | 1/31/2019 | 1/31/2019 | A | DONE |
Brian Scoles
|
|
|
please call dru 1 hr in advance so all parties can be in attendance for insulation questions. Phone #: ###-#### Inspection requested via web by Nicholas Paige- conference to discuss IECC insulation requirements- all supply, return air and outside air will need to be insulated per IECC 2015 C403.9-
|
Rough-in | 1/29/2019 | 1/30/2019 | 1/30/2019 | A | PART |
Brian Scoles
|
|
|
Fire Damper inspection Phone #: ###-#### Inspection requested via web by Nicholas Paige- area 1 a/b 10 fire damper clearances ok- area 1 a/b seal on all duct ok- ok to insulate-all insulayion needs to be according to IECC 2015- hard lids yet to be installed-
|
Conference | 1/9/2019 | 1/9/2019 | 1/9/2019 | P | DONE |
Brian Scoles
|
|
|
We have some fire dampers installed and we want to make sure the inspector likes how it is done Phone #: ###-#### Inspection requested via web by Nicholas Paige- discussed fire dampers without sleeve from factory- installation instruction are a little different from approved prints- will get more info in next day or two
|
Issue PAID IN FULL permit | | | 12/18/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/10/2018 | | DONE |
|
|
|
This permit was created on the web by Nicholas Paige
|