Final | 2/11/2019 | 2/12/2019 | 2/12/2019 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
|
Final | 2/7/2019 | 2/7/2019 | 2/7/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- need to submit manual j for approval with city and have approved city approved manuual j onsite for inspection
|
Final | 2/6/2019 | 2/6/2019 | 2/6/2019 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- equipment installed does not match manual j- need to resubmit to city and have approved manual j onsite for final inspection
|
Rough-in | 12/12/2018 | 12/13/2018 | 12/13/2018 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- R/I ok
|
Pressure Test | 12/12/2018 | 12/12/2018 | 12/12/2018 | P | PASS |
Brian Scoles
|
|
|
20lb gas pass- range csst was rerouted
|
Rough-in | 12/12/2018 | 12/12/2018 | 12/12/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- insulation shield needs to be 7" or larger to maintain 1" clearance-
|
Rough-in | 12/10/2018 | 12/11/2018 | 12/11/2018 | P | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- need approved csst nail plates at ceiling both sides at range location- need to seal dryer duct to termination box- missing supply register in walk in closet- insulation shield needs minimum 1" clearance to to b vent- left correction notice front entry window
|
Pressure Test | 12/10/2018 | 12/11/2018 | 12/11/2018 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- 20lb gas pass
|
Issue PAID IN FULL permit | | | 12/10/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/10/2018 | | DONE |
|
|
|
This permit was created on the web by GREGORY ANDERSEN
|