Inspections for the day of: Wednesday, January 31, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00670 INSP-Sprinkler Rough-in1/31/20181/31/20181/31/2018 2:42:30 PMPPART
Rough to cover inspection for overhead fire sprinkler piping located above hardlids complete, hardlids approved for cover.
BLD17-04667 FIRE-Final Inspection1/30/20181/31/20181/31/2018 12:01:25 PMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place with current inspection tags, fire sprinkler inspection tag is current, knox box is located by fire sprinkler riser as well as tenant space. Noted that north main entry has thumbturn locking hardware installed. Final life fire safety inspection complete.
FIR18-00035 INSP-Sprinkler Rough-in1/30/20181/31/20181/31/2018 10:42:18 AMAPART
Partial rough to cover inspection complete, IBR , change of direction with thrust block and approximately 20 feet of pipe approved for cover. Remaining pipe to be installed at a later date.
BLD16-03292 FIRE-Final Inspection1/30/20181/31/20181/31/2018 9:47:34 AMAFAIL
Emergency lighting that did not operate needs to be repaired and retested. Signage needs to be installed on the fire panel control room, the fire sprinkler riser room as well as signage for the dry standpipe with dry standpipe info mounted by the FDC location. Mount fire extinguishers in discussed locations and provide inspection tags for each fire extinguisher. Remove storage/combustible material from stairwells. Install glass in stairwell doors.
FIR17-00644 INSP-Final Inspection1/30/20181/31/20181/31/2018 9:43:00 AMAPASS
Final fire alarm inspection complete.
BLD16-03767 FIRE-Final Inspection1/26/20181/31/20181/31/2018 12:00:00 AMACANC
Emily Phone #: ###-####
BLD16-03292 FIRE-Final Inspection1/30/20181/31/20181/31/2018 12:00:00 AMPDONE
levels 2-5- later afternoon- Jeff Phone #: ###-####
FIR18-00067 INSP-Sprinkler Rough-in/Hydro1/30/20181/31/20181/30/2018 2:23:02 PMACANC
Fire Service Cover Inspection Phone #: ###-#### >> Inspection requested via web by Christophe Wilson Inspection cancelled from web by: Christophe Wilson