FIR17-00670
| INSP-Sprinkler Rough-in | 1/31/2018 | 1/31/2018 | 1/31/2018 2:42:30 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping located above hardlids complete, hardlids approved for cover.
|
BLD17-04667
| FIRE-Final Inspection | 1/30/2018 | 1/31/2018 | 1/31/2018 12:01:25 PM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place with current inspection tags, fire sprinkler inspection tag is current, knox box is located by fire sprinkler riser as well as tenant space. Noted that north main entry has thumbturn locking hardware installed. Final life fire safety inspection complete.
|
FIR18-00035
| INSP-Sprinkler Rough-in | 1/30/2018 | 1/31/2018 | 1/31/2018 10:42:18 AM | A | PART |
|
|
Partial rough to cover inspection complete, IBR , change of direction with thrust block and approximately 20 feet of pipe approved for cover. Remaining pipe to be installed at a later date.
|
BLD16-03292
| FIRE-Final Inspection | 1/30/2018 | 1/31/2018 | 1/31/2018 9:47:34 AM | A | FAIL |
|
|
Emergency lighting that did not operate needs to be repaired and retested. Signage needs to be installed on the fire panel control room, the fire sprinkler riser room as well as signage for the dry standpipe with dry standpipe info mounted by the FDC location. Mount fire extinguishers in discussed locations and provide inspection tags for each fire extinguisher. Remove storage/combustible material from stairwells. Install glass in stairwell doors.
|
FIR17-00644
| INSP-Final Inspection | 1/30/2018 | 1/31/2018 | 1/31/2018 9:43:00 AM | A | PASS |
|
|
Final fire alarm inspection complete.
|
BLD16-03767
| FIRE-Final Inspection | 1/26/2018 | 1/31/2018 | 1/31/2018 12:00:00 AM | A | CANC |
|
|
Emily Phone #: ###-####
|
BLD16-03292
| FIRE-Final Inspection | 1/30/2018 | 1/31/2018 | 1/31/2018 12:00:00 AM | P | DONE |
|
|
levels 2-5- later afternoon- Jeff Phone #: ###-####
|
FIR18-00067
| INSP-Sprinkler Rough-in/Hydro | 1/30/2018 | 1/31/2018 | 1/30/2018 2:23:02 PM | A | CANC |
|
|
Fire Service Cover Inspection Phone #: ###-#### >> Inspection requested via web by Christophe Wilson Inspection cancelled from web by: Christophe Wilson
|