BLD17-02477
| FIRE-Final Inspection | 10/23/2018 | 10/23/2018 | 10/24/2018 8:10:14 AM | P | PART |
|
|
The six apartments at the north end of the building life safety's are complete. Apartments 101, 102, 201, 202, 103, 203.
Cody Phone #: ###-####
|
FIR18-00548
| INSP-Final Inspection | 10/19/2018 | 10/23/2018 | 10/24/2018 8:08:59 AM | A | PART |
|
|
The 12 apartments on the north end of the building are complete.
Colton Cox (###-####) or Jon Beazer ( ###-####) are the contacts for this final inspection. They are needing the inspection on 12 of the units or half of the project. We appreciate your help. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-02633
| FIRE-Final Inspection | 10/23/2018 | 10/23/2018 | 10/23/2018 2:30:08 PM | P | FAIL |
|
|
Need the project related fire alarm permit finaled and single action hardware on the exterior office door that has the keyed lock on it.
Mark Phone #: ###-####
|
FIR18-00414
| INSP-Final Inspection | 10/22/2018 | 10/23/2018 | 10/23/2018 2:27:22 PM | A | FAIL |
|
|
The interconnections with the fire alarm system could not be tested, could not verify pressure relief vavles and the overhead doors have not been modified to remain less than 4' obstruction
Jordan Fuger is the contact for this final inspection. We appreciate your help. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-03880
| FIRE-Final Inspection | 10/22/2018 | 10/23/2018 | 10/23/2018 2:02:35 PM | P | CANC |
|
|
To be rescheduled for Thursday per Robert Phone #: ###-####
|
FIR18-00481
| INSP-Sprinkler Rough-in | 10/23/2018 | 10/23/2018 | 10/23/2018 1:49:43 PM | P | CANC |
|
|
Contact Leroy Anderson ###-#### 30 min prior to RTC Insp Start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
NAF18-00123
| INSP-Final | 10/22/2018 | 10/23/2018 | 10/23/2018 1:13:42 PM | P | CANC |
|
|
The fitter and I are unable to meet. Will need to be rescheduled
1 head Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00730
| INSP-Sprinkler Rough-in/Hydro | 10/23/2018 | 10/23/2018 | 10/23/2018 1:12:47 PM | P | PASS |
|
|
Underground supply hydro test passed
|
BLD18-01455
| FIRE-Final Inspection | 10/22/2018 | 10/23/2018 | 10/23/2018 11:04:24 AM | A | FAIL |
|
|
Fire alarm notification modifications are required for the strobe just inside of the main entry and the stobe in the main corridor. They are overspaced as set at 30cd. All other items appear ok.
Eric Phone #: ###-####
|
BLD18-01083
| FIRE-Final Inspection | 10/22/2018 | 10/23/2018 | 10/23/2018 10:22:07 AM | A | FAIL |
|
|
Plans need to be revised and re-approved for the wall layout changes. The path of egress will need to be approved for possible exit sign/emergency light layout. Also multiple open rooms in the warehouse area actuall have overhead doors installed and "porthole" type windows mounted that state "emergency exit". The doors/exiting need approved.
Jim Phone #: ###-####
|
FIR18-00012
| INSP-Final Inspection | 10/19/2018 | 10/23/2018 | 10/23/2018 9:34:11 AM | A | PASS |
|
|
permit finaled
|
FIR18-00333
| INSP-Final Inspection | 10/22/2018 | 10/23/2018 | 10/23/2018 12:00:00 AM | A | CANC |
|
|
Contact is Sean. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten
Dialer not ready yet.
|
FIR18-00081
| INSP-Final Inspection | 10/22/2018 | 10/23/2018 | 10/23/2018 12:00:00 AM | P | PASS |
|
|
This inspection is being moved from the am to the pm because Shilo needed the morning to finish up their part. Please call ###-#### to let Crane Alarm know when you''ll be meeting Peter and Shilo for the inspection in the afternoon. Phone #: ###-#### >> Inspection requested via web by Laura Tyson
Final ok once record of completion is received.
|
FIR18-00783
| INSP-Final Inspection | 10/19/2018 | 10/23/2018 | 10/23/2018 12:00:00 AM | P | PASS |
|
|
Brian - Technician Phone #: ###-#### >> Inspection requested via web by Brian Richard
Final ok once record of completion is received.
|
FIR18-00081
| INSP-Final Inspection | 10/19/2018 | 10/23/2018 | 10/22/2018 10:43:55 AM | A | CANC |
|
|
Our technician, Peter Naumov, has an appointment at 10am. We would like to have this final scheduled before that time if possible. Please call the office (###-####) when this is scheduled. Phone #: ###-#### >> Inspection requested via web by Laura Tyson Inspection cancelled from web by: Laura Tyson
|