ELE17-02293
| Electrical Rough-In | 10/23/2017 | 10/26/2017 | 10/26/2017 3:42:47 PM | P | PASS |
|
|
Zack-can only be there after 3:30 so would like inspection after taht if possible Phone #: ###-#### Master bathroom addition rough in ok cover
|
ELE17-03341
| Electrical Rough-In | 10/25/2017 | 10/26/2017 | 10/26/2017 2:45:49 PM | P | FAIL |
|
|
Michael Donelson ###-#### Above Grid/ceiling inspection Phone #: ###-#### Inspection requested via web by Samatha Solberg 300.15- All cables shall terminate in a box. MC above grid in wellnes room. 314.17(A)- Unused openings shall be sealed. Several connectors left in boxes and open KOs. 314.22(E)- Boxes mounted on support wires shall be secured at both ends and taut. Called contact and left message.
|
ELE17-02119
| Final | 10/25/2017 | 10/26/2017 | 10/26/2017 1:30:17 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tracy Robertson Final ok
|
ELE17-01837
| Electrical Rough-In | 10/26/2017 | 10/26/2017 | 10/26/2017 11:29:44 AM | P | PASS |
|
|
Canopy vestibule area Phone #: ###-#### Inspection requested via web by Tom Jenkins South vestibule ceiling rough in ok cover
|
ELE17-03606
| Temporary Service | 10/25/2017 | 10/26/2017 | 10/26/2017 11:01:51 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson t/s o/h n ok
|
ELE17-03603
| Temporary Service | 10/25/2017 | 10/26/2017 | 10/26/2017 11:01:16 AM | A | PASS |
|
|
Overhead Power Pole Phone #: ###-#### Inspection requested via web by Dean Gernaat t/s o/h n ok
|
ELE17-02190
| Final | 10/25/2017 | 10/26/2017 | 10/26/2017 10:46:49 AM | A | PASS |
|
|
Back door behind garage is unlocked. Phone #: ###-#### Inspection requested via web by Dean Gernaat Final ok
|
ELE17-03200
| Electrical Rough-In | 10/25/2017 | 10/26/2017 | 10/26/2017 10:43:33 AM | A | FAIL |
|
|
Lock Box Code 1811 Phone #: ###-#### Inspection requested via web by Dean Gernaat 210.52- Receptacle outlets shall be installed so that no point measured along floor line is more than 6' from a receptacle outlet. Small front room 1 needed with in 6' of door and front bed window wall. 300.4(E)- Cable shall not be installed above fir strips for roof. front bed 14-2 above rafters, potential damage from roofing.
|
ELE17-01837
| Electrical Rough-In | 10/25/2017 | 10/26/2017 | 10/26/2017 9:48:01 AM | A | FAIL |
|
|
Rough in ceiling for canopies on South wall. Heaters and can lights Phone #: ###-#### Inspection requested via web by Tom Jenkins 300.4(E)- Cables shall not be installed with in 1 1/2" of roof deck. 314.17(A)- Unused openings shall be sealed. East can junction box.
|
ELE17-01549
| Electrical Rough-In | 10/25/2017 | 10/26/2017 | 10/26/2017 9:04:42 AM | A | PASS |
|
|
10 AM POUR. LINEAR LIGHTS. SHANE IS THE CONTACT HIS CELL NO. IS ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates 3 lights included in this southwest pour. Rough in ok cover
|
ELE17-03283
| Electrical Rough-In | 10/24/2017 | 10/26/2017 | 10/26/2017 12:00:00 AM | P | CANC |
|
|
Want a final instead Call Brad if any questions Phone #: ###-#### >> Inspection requested via web by Christian Kilpatrick
|