Inspections for the day of: Thursday, October 26, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02293 Electrical Rough-In10/23/201710/26/201710/26/2017 3:42:47 PMPPASS
Zack-can only be there after 3:30 so would like inspection after taht if possible Phone #: ###-####
Master bathroom addition rough in ok cover
ELE17-03341 Electrical Rough-In10/25/201710/26/201710/26/2017 2:45:49 PMPFAIL
Michael Donelson ###-####
Above Grid/ceiling inspection Phone #: ###-#### Inspection requested via web by Samatha Solberg
300.15- All cables shall terminate in a box. MC above grid in wellnes room.
314.17(A)- Unused openings shall be sealed. Several connectors left in boxes and open KOs.
314.22(E)- Boxes mounted on support wires shall be secured at both ends and taut.
Called contact and left message.
ELE17-02119 Final10/25/201710/26/201710/26/2017 1:30:17 PMAPASS
Phone #: ###-#### Inspection requested via web by Tracy Robertson
Final ok
ELE17-01837 Electrical Rough-In10/26/201710/26/201710/26/2017 11:29:44 AMPPASS
Canopy vestibule area Phone #: ###-#### Inspection requested via web by Tom Jenkins
South vestibule ceiling rough in ok cover
ELE17-03606 Temporary Service10/25/201710/26/201710/26/2017 11:01:51 AMPPASS
Phone #: ###-#### Inspection requested via web by Ryan Wilson
t/s o/h n ok
ELE17-03603 Temporary Service10/25/201710/26/201710/26/2017 11:01:16 AMAPASS
Overhead Power Pole Phone #: ###-#### Inspection requested via web by Dean Gernaat t/s o/h n ok
ELE17-02190 Final10/25/201710/26/201710/26/2017 10:46:49 AMAPASS
Back door behind garage is unlocked. Phone #: ###-#### Inspection requested via web by Dean Gernaat Final ok
ELE17-03200 Electrical Rough-In10/25/201710/26/201710/26/2017 10:43:33 AMAFAIL
Lock Box Code 1811 Phone #: ###-#### Inspection requested via web by Dean Gernaat
210.52- Receptacle outlets shall be installed so that no point measured along floor line is more than 6' from a receptacle outlet. Small front room 1 needed with in 6' of door and front bed window wall.
300.4(E)- Cable shall not be installed above fir strips for roof. front bed 14-2 above rafters, potential damage from roofing.
ELE17-01837 Electrical Rough-In10/25/201710/26/201710/26/2017 9:48:01 AMAFAIL
Rough in ceiling for canopies on South wall. Heaters and can lights Phone #: ###-#### Inspection requested via web by Tom Jenkins
300.4(E)- Cables shall not be installed with in 1 1/2" of roof deck.
314.17(A)- Unused openings shall be sealed. East can junction box.
ELE17-01549 Electrical Rough-In10/25/201710/26/201710/26/2017 9:04:42 AMAPASS
10 AM POUR. LINEAR LIGHTS. SHANE IS THE CONTACT HIS
CELL NO. IS ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
3 lights included in this southwest pour. Rough in ok cover
ELE17-03283 Electrical Rough-In10/24/201710/26/201710/26/2017 12:00:00 AMPCANC
Want a final instead Call Brad if any questions Phone #: ###-#### >> Inspection requested via web by Christian Kilpatrick