Inspections for the day of: Monday, October 29, 2018.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-03009 FIRE-Final Inspection10/29/201810/29/201810/29/2018 2:56:48 PMPPASS
No fire sprinklers, smoke detector is stand-alone and not monitored, fire exitnguisher is placed with current inspection tag. Final life fire safety inspection for area of work complete.

Please call 30 mins ahead of time so I can meet you there. Phone #: ###-#### Inspection requested via web by Gerome Fries
BLD18-01760 FIRE-Final Inspection10/29/201810/29/201810/29/2018 2:23:53 PMPPASS
Final life fire safety inspection for area of work complete.

Derek Phone #: ###-####
BLD18-01760 FIRE-Final Inspection10/26/201810/29/201810/29/2018 2:23:15 PMACANC
zack Phone #: ###-####
FIR18-00512 INSP-Sprinkler Rough-in/Hydro10/29/201810/29/201810/29/2018 1:47:31 PMPDONE
Hydrostatic test for undergorund supply witnessed, no pressure loss observed.

this is a underground hydro test.
troy is our contact Phone #: ###-#### Inspection requested via web by Brad Bettencourt
BLD17-04365 FIRE-Final Inspection10/29/201810/29/201810/29/2018 1:46:47 PMPFAIL
City approved drawings and small documentation not on site, city approved drawings and associated small documents are required for the inspection process. Performed courtesy inspection for basic life safety items, no emergency lighting in shower/restroom area. Fire alarm modifications are required for area of work as noted in the fire conference notes entered in on 9JULY2018 under this BLD permit.

Fire alarm panel was showing a trouble at time of inspection, fire alarm panel needs to show a normal panel before life fire safety inspection.

John or ###-#### Breanna Phone #: ###-####
BLD18-00923 FIRE-Final Inspection10/29/201810/29/201810/29/2018 11:46:03 AMPPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags, commercial hood fire suppression system inspection complete. Final life fire safety inspection for area of work complete.
FIR18-00774 INSP-Final Inspection10/29/201810/29/201810/29/2018 11:44:44 AMPPASS
Final fire alarm inspection for area of work complete.

Shyann Phone #: ###-####
FIR18-00819 INSP-Sprinkler Rough-in10/29/201810/29/201810/29/2018 11:27:20 AMPPASS
Rough to cover ispection for overhead fire sprinkler piping in area of work complete, approved for cover.

rick Phone #: ###-####
FIR18-00736 INSP-Final Inspection10/29/201810/29/201810/29/2018 11:12:47 AMAPASS
Final fire alarm inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Rick Groom
FIR18-00459 INSP-Final Inspection10/29/201810/29/201810/29/2018 11:09:35 AMPPASS
Final fire sprinkler inspection for scope of work complete.

rick Phone #: ###-####
FIR18-00636 INSP-Sprinkler Rough-in10/29/201810/29/201810/29/2018 11:07:42 AMAPASS
All tenting in place at time of inspection, overehad fire sprinkler piping rough in complete, overhead fire sprinkler piping approved for cover.
FIR18-00636 INSP-Sprinkler Rough-in/Hydro10/26/201810/29/201810/29/2018 11:06:53 AMADONE
Hydrostatic test for overhead fire sprinkler piping on levels 1, 2 and 3 witnessed, no pressure loss observed at riser provided gauges. Noted that glycerin anti-freeze was used to complete hydrostatic test.

Phone #: ###-#### Inspection requested via web by Stan Beus
BLD18-02561 FIRE-Final Inspection10/29/201810/29/201810/29/2018 11:02:41 AMPPASS
Life fire safety inspection for racking permit associated with tenant complete. Final life fire safety inspection for area of work complete.
FIR18-00716 INSP-Sprinkler Rough-in10/26/201810/29/201810/29/2018 11:01:46 AMAPART
Rough to cover inspection for overhead fire sprinkler piping on levels 1 and 2 complete, levels 1 and 2 approvbed for cover. Rough in inspection for level 3 complete, tenting still needs to be installed, level 3 not approved for cover.

Phone #: ###-#### Inspection requested via web by Stan Beus
BLD18-03747 FIRE-Final Inspection10/23/201810/29/201810/29/2018 10:04:04 AMAPASS
Life fire safety inspection for racking permit complete.

brandon Phone #: ###-####
FIR18-00737 INSP-Final Inspection10/29/201810/29/201810/29/2018 8:54:22 AMAPASS
Final fire alarm inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Rick Groom
FIR18-00774 INSP-Final Inspection10/26/201810/29/201810/29/2018 8:53:44 AMAFAIL
Called phone number provided two times between 0820 and 0845, received a messgae stated it was outside of normal business hours. Inspection request will need to be rescheduled.

Shyann Phone #: ###-####
BLD18-01325 FIRE-Final Inspection10/26/201810/29/201810/29/2018 7:42:58 AMAPASS
Final life fire safety inspection for area of work complete.

Rick Phone #: ###-####