Inspections for the day of: Wednesday, October 30, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00486 FIR-Aging Inspection10/30/201910/30/201911/7/2019 10:37:28 AM CANC
BLD19-04191 FIRE-Final Inspection10/29/201910/30/201910/30/2019 2:24:57 PMPFAIL
Remove surface mount slide bolt on main entry. Provide signage on the inside of the main entry reading "Door to remain unlocked while building is occupied". Provide code compliant addressing as discussed on the address side of the street.

Call for access- Delia Phone #: ###-####
BLD19-04245 FIRE-Final Inspection10/30/201910/30/201910/30/2019 12:58:05 PMPFAIL
Audio system that will be installed will be able to overpower the fire alarm notification in tenant space, provide means to isolate sound from audio equipment during a fire alarm event per section 18.4 of the 2016 NFPA 72, a permit will be required for fire alarm modifications.

call 30 to an hour for access- Russell Phone #: ###-####
BLD19-00871 FIRE-Final Inspection10/28/201910/30/201910/30/2019 10:42:32 AMAFAIL
FIR permit for fire alarms needs to be finaled before life fire safety inspection can be completed. Notated city approved drawings where plans show exit lights but exit lights are not installed. Notated city approved drawings where a fire extinguisher is shown but is not in place.

Tom Phone #: ###-####
FIR19-00441 INSP-Final Inspection10/25/201910/30/201910/30/2019 10:40:57 AMAFAIL
Provide weather proof A/V devices in restrooms that have showers as discussed.

Fire Alarm Final - verify annunciator functional. Phone #: ###-#### Inspection requested via web by Brian Richard
FIR19-00306 INSP-Final Inspection10/28/201910/30/201910/30/2019 10:34:49 AMAPASS
Final fire sprinkler inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00682 INSP-Final Inspection10/28/201910/30/201910/30/2019 8:57:29 AMAFAIL
Insulation above ceiling hanging down blocking upright head. 410 escutcheon missing in corridor leading to back door.

Call James before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00664 INSP-Final Inspection10/29/201910/30/201910/30/2019 8:38:48 AMAPASS
Final fire sprinkler inspection for scope of work complete.

Soffits are all closed up Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00404 INSP-Final Inspection10/29/201910/30/201910/30/2019 8:38:01 AMAFAIL
Provide annual inspection for backflow assembly. Repair visible leak at bottom of backflow.

Bobbie Silva is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00817 INSP-Final Inspection10/29/201910/30/201910/29/2019 4:10:46 PMPCANC
Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson Inspection cancelled via mobile web on Tuesday, October 29, 2019.