FIR13-00486
| FIR-Aging Inspection | 10/30/2019 | 10/30/2019 | 11/7/2019 10:37:28 AM | | CANC |
|
|
|
BLD19-04191
| FIRE-Final Inspection | 10/29/2019 | 10/30/2019 | 10/30/2019 2:24:57 PM | P | FAIL |
|
|
Remove surface mount slide bolt on main entry. Provide signage on the inside of the main entry reading "Door to remain unlocked while building is occupied". Provide code compliant addressing as discussed on the address side of the street.
Call for access- Delia Phone #: ###-####
|
BLD19-04245
| FIRE-Final Inspection | 10/30/2019 | 10/30/2019 | 10/30/2019 12:58:05 PM | P | FAIL |
|
|
Audio system that will be installed will be able to overpower the fire alarm notification in tenant space, provide means to isolate sound from audio equipment during a fire alarm event per section 18.4 of the 2016 NFPA 72, a permit will be required for fire alarm modifications.
call 30 to an hour for access- Russell Phone #: ###-####
|
BLD19-00871
| FIRE-Final Inspection | 10/28/2019 | 10/30/2019 | 10/30/2019 10:42:32 AM | A | FAIL |
|
|
FIR permit for fire alarms needs to be finaled before life fire safety inspection can be completed. Notated city approved drawings where plans show exit lights but exit lights are not installed. Notated city approved drawings where a fire extinguisher is shown but is not in place.
Tom Phone #: ###-####
|
FIR19-00441
| INSP-Final Inspection | 10/25/2019 | 10/30/2019 | 10/30/2019 10:40:57 AM | A | FAIL |
|
|
Provide weather proof A/V devices in restrooms that have showers as discussed.
Fire Alarm Final - verify annunciator functional. Phone #: ###-#### Inspection requested via web by Brian Richard
|
FIR19-00306
| INSP-Final Inspection | 10/28/2019 | 10/30/2019 | 10/30/2019 10:34:49 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00682
| INSP-Final Inspection | 10/28/2019 | 10/30/2019 | 10/30/2019 8:57:29 AM | A | FAIL |
|
|
Insulation above ceiling hanging down blocking upright head. 410 escutcheon missing in corridor leading to back door.
Call James before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00664
| INSP-Final Inspection | 10/29/2019 | 10/30/2019 | 10/30/2019 8:38:48 AM | A | PASS |
|
|
Final fire sprinkler inspection for scope of work complete.
Soffits are all closed up Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00404
| INSP-Final Inspection | 10/29/2019 | 10/30/2019 | 10/30/2019 8:38:01 AM | A | FAIL |
|
|
Provide annual inspection for backflow assembly. Repair visible leak at bottom of backflow.
Bobbie Silva is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00817
| INSP-Final Inspection | 10/29/2019 | 10/30/2019 | 10/29/2019 4:10:46 PM | P | CANC |
|
|
Phone #: 2086157641 >> Inspection requested via mobile web by Richard Johnson Inspection cancelled via mobile web on Tuesday, October 29, 2019.
|