Inspections for the day of: Monday, October 31, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00689 INSP-Final Inspection10/31/201610/31/201610/31/2016 3:54:56 PMPPASS
Permit finaled. Sidewall heads modified to extend beyond the columns that had been blocking them
FIR16-00680 INSP-Final Inspection10/25/201610/31/201610/31/2016 2:35:07 PMPPASS
Phone #: ###-#### Inspection requested via web by Don Kartchner
BLD16-03806 FIRE-Final Inspection10/28/201610/31/201610/31/2016 2:34:51 PMAFAIL
No city approved plans on site. No inspection performed.
FIR15-00727 INSP-Final Inspection10/31/201610/31/201610/31/2016 2:34:25 PMPFAIL
The two new window sprinklers are not installed as per the installation guide for distance below the window mullion. Also before a final sign off the signage the describes the area serviced by the FDC's need to be installed. Scott and I discussed final sign offs.
FIR16-00598 INSP-Final Inspection10/28/201610/31/201610/31/2016 11:15:42 AMPCANC
Morgan Phone #: ###-#### Inspection cancelled from web by: Morgan Ahten
BLD16-02895 FIRE-Final Inspection10/28/201610/31/201610/31/2016 9:23:22 AMAPASS
Life safety passed
FIR16-00680 INSP-Final Inspection10/30/201610/31/201610/31/2016 9:22:53 AMAPASS
Permit finaled. Hood suppression system functioned correctly
FIR15-00699 INSP-Final Inspection10/28/201610/31/201610/31/2016 8:56:15 AMAPASS
Permit finaled