Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00609 INSP-Sprinkler Rough-in/Hydro10/8/201810/9/201810/9/2018 2:07:38 PMPPART
Bury depth has been corrected. Underground supply piping can be covered. Not ready for hydro test yet.

Underground, 2hr hydro - Robert Phone #: ###-####
FIR18-00768 INSP-Final Inspection10/9/201810/9/201810/9/2018 2:03:00 PMPPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR16-00563 INSP-Sprinkler Rough-in/Hydro10/8/201810/9/201810/9/2018 11:28:42 AMAPASS
Overhead hydro for the 4th and 5th floors witnessed with no visible loss at the guages.


Please coordinate hydro with Lonnie Greenfield Phone #: ###-#### Inspection requested via web by Christophe Wilson
BLD18-01767 FIRE-Final Inspection10/8/201810/9/201810/9/2018 10:13:01 AMAFAIL
Life safety will be ok to pass when a fire alarm permit is issued/passed for the required modifications. I noted three areas where notification needs to be modified.


call before when on way// Michael Phone #: ###-####
FIR18-00732 INSP-Final Inspection10/4/201810/9/201810/8/2018 5:44:52 PMACANC
Ray McQueen, inspecting technician, building access is open Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson