Inspections for the day of: Tuesday, November 12, 2019.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03670 ELE-Aging Inspection11/12/201911/12/201911/15/2019 12:44:31 PM PASS
Called office who said they would pass on info to shop.
ELE17-03806 ELE-Aging Inspection11/12/201911/12/201911/15/2019 12:39:02 PM PASS
Contacted Jason, he said he would contact owner of house and schedule final.
ELE15-00102 DOC - Permit Expired11/12/201911/12/201911/12/2019 3:59:56 PMPPASS
Doc expired ok
ELE19-04278 Final11/12/201911/12/201911/12/2019 3:52:36 PMPPASS
Home Owner Stated All Issues On Work By Others Resolved I Will Have My Corrections Resolved And Finished Thanks For Your Help Phone #: ###-#### Inspection requested via web by jason shifflett
Confirmed with building inspector other permitting issues being handled. Final ok
ELE19-04379 Permanent Service11/12/201911/12/201911/12/2019 3:34:16 PMPFAIL
Call for access- Roy Phone #: ###-####
Too many violations to list, 200 main breaker panel installed where a 125 amp main breaker panel had failed. 125 amp mete base not changed, mast left original, Deck built around old existing meter base.
Explained reason for conference, owner understood but decided to for go to save time.
ELE19-04379 Conference11/12/201911/12/201911/12/2019 3:34:07 PMPDONE
Call for access- Roy Phone #: ###-####
Discussed minimums required for change out of interior main breaker panel, Work space shall be provided for meter base and interior panel, 2" IMC minimum shall be installed for service mast used to support power swing. 2/0 copper conductors or 4/0 aluminum minimum shall be installed for service entrance conductors, Unable to verify metal underground water pipe so minimum of 2 ground rods shall be installed with #6 copper grounding electode conductor. Main bonding jumper screw shall be installed. Discussed bonding issuew with metal nipple verses non-metallic. Discussed minimum support required for service mast.
Discussed other issues found in mechanical/ utility room, Dryer branch circuit shall terminate in a box as per 300.15 and basement range shall have sheathing installed in box at least 1/4". Seperate traveller ran on exterior of other NM cable in 3-way switch, red conductor. Must fix these issues by final.
ELE19-04338 Electrical Rough-In11/12/201911/12/201911/12/2019 2:08:10 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Due to shortage of materials all recessed luminaires to be listed cut-in type cans. Soffits and hardlids rough in ok cover
ELE19-02436 Final11/10/201911/12/201911/12/2019 1:01:10 PMAPASS
Back door will be unlocked for entry Phone #: ###-#### Inspection requested via web by Tyler Ridley
All areas finishes not complete but electrical all safe. Final ok
ELE19-04341 Conference11/8/201911/12/201911/12/2019 12:21:31 PMAPASS
Phone #: ###-#### Inspection requested via web by Gary Betts
Owner is an electrical engineer, good understanding of scope of work. Discussed type of receptacles required, TR, WR, GFCI, flappers ok under cover, single circuit no grounding electrode required, shall be sch.80 where emerge from grade under meter main, NM cable ok in cabinet where protected form moisture. Trench to be 90% under pavers, depth ok
ELE19-04242 Rough-In Permanent Service11/8/201911/12/201911/12/2019 11:16:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt
Rough in ok cover p/s u/g n ok
ELE19-04294 Temporary Service11/8/201911/12/201911/12/2019 11:04:46 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
250.68(B)- Connection to grounding electrode shall be tight to provide an effective ground path. Acorn on transformer post loose.
ELE19-04177 Temporary Service11/11/201911/12/201911/12/2019 10:47:19 AMAPASS
Corbin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
Service to be reconnected on a temporary basis due to transformer and meter base will have to move when road widening project begins.
t/s u/g rec ok
ELE19-00602 Electrical Rough-In11/11/201911/12/201911/12/2019 10:00:41 AMAPASS
SE Stair tower in garage. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Stairway noted pour rough in ok cover
ELE19-00601 Electrical Rough-In11/11/201911/12/201911/12/2019 9:59:58 AMAPASS
3rd Floor hotel room cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 3 rooms 302 thru 324 rough in ok cover
ELE19-04338 Electrical Rough-In11/8/201911/12/201911/12/2019 9:10:18 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Walls only rough in ok cover
ELE19-03235 Electrical Rough-In11/11/201911/12/201911/12/2019 8:48:29 AMANR
Electrical Rough in for walls. Phone #: ###-#### Inspection requested via web by Deb Ipsen
Unable to inspect until a building permit has been issued for work taking place.
ELE19-03585 Electrical Rough-In11/11/201911/12/201911/12/2019 8:41:19 AMAPASS
Bathroom ceiling Phone #: ###-#### Inspection requested via web by Jim Williams
No changes to bathroom walls. Both bathroom walls and ceilings rough in ok cover