Inspections for the day of: Tuesday, November 19, 2013.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00233 INSP-Final Inspection11/14/201311/19/201311/20/2013 4:43:18 PMAPART
elevator only - Jonathan Phone #: ###-#### *State elevator inspection- Offsite monitoring NR
BLD13-01332 FIRE-Final Inspection11/19/201311/19/201311/20/2013 4:36:36 PMPNR
Need to post building address numbers, missing main entry door, project finishes underway, approved plans not available on site. Project is not in condition for final fire life safety inspection.
FIR13-00544 INSP-Sprinkler Rough-in11/19/201311/19/201311/19/2013 3:54:29 PMPPART
Okay to cover overhead work at the grid ceiling areas. Verified new QR heads have been installed per the scope indicated. Noted one head at the elevator lobby to be replaced with an intermediate temp or relocated away from the heat register.
FIR13-00075 INSP-Sprinkler Rough-in/Hydro11/18/201311/19/201311/19/2013 2:50:00 PMPPART
Overhead hydrostatic test of new system piping completed and passed.
BLD13-01020 FIRE-Final Inspection11/14/201311/19/201311/19/2013 2:47:27 PMPPASS
Final fire life safety inspection completed acceptable. New address numbers to be posted as discussed.
BLD13-02942 FIRE-Final Inspection11/18/201311/19/201311/19/2013 2:45:53 PMAPASS
Fire life safety inspection passed- Exit sign at the main entry repaired while on site.
FIR13-00627 INSP-Final Inspection11/19/201311/19/201311/19/2013 2:44:11 PMPPASS
Fire sprinkler permit finaled.
FIR13-00652 INSP-Final Inspection11/19/201311/19/201311/19/2013 2:43:10 PMPPASS
Scope of fire alarm work completed and passed inspection. Permit finaled.
BLD13-02942 FIRE-Alarm Testing11/18/201311/19/201311/19/2013 2:40:55 PMADONE
Fire alarm testing completed.