Inspections for the day of: Wednesday, November 22, 2017.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00852 ELE-Aging Inspection11/22/201711/22/201711/28/2017 11:03:13 AM PASS
See notes listed on final.
ELE17-02120 Final11/21/201711/22/201711/22/2017 2:16:18 PMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall Ok final.
ELE16-02878 Final11/21/201711/22/201711/22/2017 1:55:23 PMAPASS
Sign present with disconnect.
ELE16-03618 Final11/21/201711/22/201711/22/2017 1:54:45 PMAPASS
Sign present with UL and disconnect.
ELE17-03705 Electrical Rough-In11/22/201711/22/201711/22/2017 1:16:36 PMPPASS
Rick Phone #: ###-#### Ok cover new home.
ELE17-03705 Permanent Service11/22/201711/22/201711/22/2017 1:16:06 PMPPASS
p/s u/g n ok
ELE17-03952 Final11/21/201711/22/201711/22/2017 12:45:35 PMPPASS
PLEASE CONTACT MICK THE ELECTRICIAN FOR ANY QUESTIONS ###-#### Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON Ok final. Generac system. Grounds/neutrals bonded in Generac panel, seperated in house panel. Generator powered by 70a brkr in unit itself.
ELE16-04165 Electrical Rough-In11/21/201711/22/201711/22/2017 12:19:31 PMPPASS
The contractor will be there until 3pm. His name is Mike Bean. The soffit lights and plugs are ready on the back of the house. I have the "firehats" installed. Phone #: ###-#### Inspection requested via web by Craig Korell Ok cover 14 cans in soffit. All cans have fire hats.
ELE17-03951 Electrical Rough-In11/22/201711/22/201711/22/2017 11:35:18 AMPPASS
Contact: Jacob Giese - underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Ok cover. Received pics from contractor. Depth is per code.
ELE17-03962 Electrical Rough-In11/21/201711/22/201711/22/2017 10:00:27 AMAPASS
This Is A Wall Inspection For Cover Only Ill Have The Ceiling Done Next Week.The Space Is Unoccupied And The Lock Box Code Is 4290. Please Call With Any Questions Or Concerns Thanks And Have A Happy Thanksgiving! Dave ###-#### Phone #: ###-#### Inspection requested via web by jason shifflett Ok cover. Conference room is 216 sq ft. 210.71(B)(2) states if it is over 215 it has to have floor outlet. With this small difference in floor space I will not require a floor outlet to be installed due to extensive cost for concrete work. Number of outlets required meets 210.52(A)(2).
ELE17-03739 Final11/21/201711/22/201711/22/2017 9:27:59 AMAPASS
Pls call Bryce (Foreman) @ ###-#### or George (Electrician) @ ###-#### 1 hr prior or if you have any questions. Thank you. Inspection requested via web by Christian Kilpatrick Ok final. All components labeled per code. Riser from underground to meter needed fixed do to damage. 2" was pulled out of the bottom of meter base, an expansion coupling was installed
ELE17-00620 Final11/21/201711/22/201711/22/2017 9:04:04 AMAPASS
Please call ahead for access - Robert Phone #: ###-#### Ok final.
ELE17-03961 Electrical Rough-In11/21/201711/22/201711/22/2017 8:46:47 AMAPASS
inspect under ground conduit for cover,Thanks Phone #: ###-#### Inspection requested via web by Robert Schroder Ok cover ground work.
ELE17-03960 Electrical Rough-In11/21/201711/22/201711/22/2017 8:46:22 AMAPASS
inspect under ground conduit for cover, Thanks Phone #: ###-#### Inspection requested via web by Robert Schroder Ok cover ground work.
ELE13-02870 ELE-Aging Inspection11/22/201711/22/201711/22/2017 7:50:56 AM DONE
Please call to schedule a final inspection.
ELE13-01450 ELE-Aging Inspection11/22/201711/22/201711/22/2017 7:49:51 AM DONE
Please call to schedule a final inspection.
ELE17-03950 Electrical Rough-In11/21/201711/22/201711/21/2017 1:14:39 PMACANC
Requesting trench and conduit inspection Phone #: ###-#### >> Inspection requested via web by Dean Gernaat Inspection cancelled from web by: Dean Gernaat