BLD17-02477
| FIRE-Conference | 11/6/2018 | 11/6/2018 | 11/6/2018 3:15:47 PM | P | DONE |
|
|
I spoke to Cody about needing more clearance for the FDC. I have involved Ron with the Boise Fire Dept with this issue.
|
FIR18-00628
| INSP-Final Inspection | 11/6/2018 | 11/6/2018 | 11/6/2018 2:20:54 PM | P | PASS |
|
|
Permit finaled
|
FIR18-00675
| INSP-Sprinkler Rough-in/Hydro | 11/5/2018 | 11/6/2018 | 11/6/2018 2:07:04 PM | P | PART |
|
|
Rough in for the underground supply line passed and the piping can be covered./ The Hydro for underground dedicated fire main failed due to visible loss at the guage.. Contact is Cesar Rodriguez Phone #: ###-#### Inspection requested via web by Brett Lawatch
|
FIR18-00420
| INSP-Sprinkler Rough-in | 11/5/2018 | 11/6/2018 | 11/6/2018 1:25:02 PM | A | PASS |
|
|
5th floor bathroom and Lobby, see marked approved plans, piping is ok to cover.
|
FIR17-00708
| FIR-Aging Inspection | 11/5/2018 | 11/6/2018 | 11/6/2018 12:33:38 PM | A | FAIL |
|
|
Rings have been provided around the pendant heads which need approval from the manufacture. Need warning signs at the riser as per the approved plans. Flow switch functioned and rang the outside alarm bell.
Todd Phone #: ###-####
|
FIR18-00686
| INSP-Sprinkler Rough-in | 11/5/2018 | 11/6/2018 | 11/6/2018 12:29:23 PM | A | FAIL |
|
|
See the city approved plans for locations/rooms in the east half of the basement that was inspected today. As-builts are required, approval is needed for supplying the pendants in the corridor from a 1 1/2" branchline instead of the 3" main, verification is needed for combustible concealed spaces above the ceiling as discussed, need verification of spacing of sidewall heads from the walls they are installed against, need branchline restraints, need earthquake bracing installed, need flat faced bushing changed.
Basement // Ron Phone #: ###-####
|
BLD18-02924
| FIRE-Final Inspection | 11/5/2018 | 11/6/2018 | 11/6/2018 11:29:10 AM | A | PASS |
|
|
Life safety passed
Phone #: ###-#### Inspection requested via web by Rick Reynolds
|
FIR18-00702
| INSP-Final Inspection | 11/5/2018 | 11/6/2018 | 11/6/2018 11:28:35 AM | A | PASS |
|
|
Permit finaled
Rick Phone #: ###-####
|
NAF18-00050
| INSP-Supply line flush | 11/2/2018 | 11/6/2018 | 11/6/2018 10:24:07 AM | A | PASS |
|
|
The underground supply piping flush passsed
|
FIR18-00486
| INSP-Final Inspection | 11/5/2018 | 11/6/2018 | 11/6/2018 10:05:35 AM | A | PASS |
|
|
Permit finaled
|
FIR18-00311
| INSP-Sprinkler Rough-in | 11/5/2018 | 11/6/2018 | 11/6/2018 9:38:59 AM | P | CANC |
|
|
Tenting inspection Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
FIR18-00311
| INSP-Sprinkler Rough-in/Hydro | 11/5/2018 | 11/6/2018 | 11/6/2018 9:38:53 AM | A | CANC |
|
|
Call Anthony before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
BLD18-00974
| FIRE-Final Inspection | 11/5/2018 | 11/6/2018 | 11/6/2018 8:02:40 AM | A | PASS |
|
|
Life safety passed. Exit sign to be installed in warehouse prior to the building inspection as discussed.
Cody Phone #: ###-####
|
FIR18-00570
| INSP-Final Inspection | 11/5/2018 | 11/6/2018 | 11/6/2018 7:59:04 AM | A | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Ken Webster
|
FIR18-00738
| INSP-Sprinkler Rough-in/Hydro | 11/5/2018 | 11/6/2018 | 11/6/2018 7:24:25 AM | P | CANC |
|
|
UG Hydro for 8" service. Please call Troy With time frame. Phone #: ###-#### >> Inspection requested via web by Jeff Packham Inspection cancelled from web by: Jeff Packham
|
FIR18-00410
| INSP-Final Inspection | 10/30/2018 | 11/6/2018 | 11/6/2018 12:00:00 AM | A | CANC |
|
|
Hi Jim If possible we would like to start the inspection at 7:00 am. Would you please call and let me know if that is doable? Thanks Mike Timmerman Phone #: ###-#### >> Inspection requested via web by Neal Timmerman
Mike will schedule a new date with the owner, as they need an early start and time to plan. Expecting Wednesday or Thursday morning at 7:00 am.
|
FIR18-00436
| INSP-Final Inspection | 11/5/2018 | 11/6/2018 | 11/6/2018 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Gary Gambino
All functioned properly. Smoke detector on stairwell side of Won Door should have been originally installed but was approved without.
|
FIR18-00733
| INSP-Final Inspection | 11/5/2018 | 11/6/2018 | 11/6/2018 12:00:00 AM | A | CANC |
|
|
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### >> Inspection requested via web by david davis
Rescheduling for 8:00 am Wednesday morning.
|
FIR18-00515
| INSP-Final Inspection | 11/5/2018 | 11/6/2018 | 11/6/2018 12:00:00 AM | A | CANC |
|
|
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### >> Inspection requested via web by david davis.
Rescheduling for 8:00 am Wednesday morning.
|
FIR18-00683
| INSP-Final Inspection | 11/5/2018 | 11/6/2018 | 11/6/2018 12:00:00 AM | A | CANC |
|
|
Dave Phone #: ###-####
Rescheduling for 8:00 am Wednesday morning.
|