Inspections for the day of: Wednesday, December 6, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03784 Permanent Service12/6/201712/6/201712/6/2017 2:34:46 PMPCANC
Service inspection for MDP and MC Inspection requested via web by Debby Pierce
Wrong permit requested, service is associated with entire building. Needed
ELE16-04017
ELE16-04017 Permanent Service12/6/201712/6/201712/6/2017 2:34:19 PMPFAIL
110.24- Available fault current shall be posted prior to permenant service inspection. George will call with value, sticker on meter. 64k rated main breakers installed.
ELE17-02821 Final12/5/201712/6/201712/6/2017 12:40:39 PMAFAIL
Ron Phone #: ###-####
210.8- All 120 volt receptacle outlets located in unfinished basement areas shall have GFCI protection. Recept. to left of panel.
250.32- Seperate building grounding electrode system, underground metal water pipe shall be supplemented by additional rod or pipe as per 250.53(A)(2). As per conversation with 345 issue discussed on rough in and equipment ground and underground metal water pipe all required. Disregard supplemental at house panel.
300.4- NM cable where enters enclosure shall have abrasion protection. 12-2 back of service panel.
408.4- Label garage circuit.
ELE17-02493 Final12/5/201712/6/201712/6/2017 11:21:40 AMAFAIL
Key over garage man door Phone #: ###-#### Inspection requested via web by Emmet Bushman
110.3- Basement bar GFCI will not hold.
680.11- Underground wiring shall not be installed under hot tub. Feed from garage service to sub fed house under hot tub.
ELE16-03933 Electrical Rough-In12/5/201712/6/201712/6/2017 10:08:59 AMAPASS
kitchen walls, dropped ceilings live works 101-105 Phone #: ###-#### Inspection requested via web by Cathy Duchek
101 not ready, 102 thru 105 live works walls and drop lids rough in ok cover
ELE17-03957 Electrical Rough-In12/5/201712/6/201712/6/2017 9:26:55 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Island wall rough in ok cover
ELE17-02732 Electrical Rough-In12/5/201712/6/201712/6/2017 9:26:19 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Inspection request was for IT room grid. 314.29- HVAC unit located above grid in IT room blocksan existing access door to elevator shaft that has electrical boxes. HVAC unit shall be located so access door can be opened 90 degrees for access.
400.12- Flexible cords shall not be installed above grid. Sump pump power cord shall not pass thru or be installed above grid.
ELE17-01549 Electrical Rough-In12/5/201712/6/201712/6/2017 8:48:49 AMAPASS
Shane is the contact his cell no.is ###-####.Historic pole lights on Main Street. Phone #: ###-#### Inspection requested via web by Shawna Gates
Request will need public works approval. Underground and pole bases for south west of parking garage entrance rough in ok cover.