ELE17-03784
| Permanent Service | 12/6/2017 | 12/6/2017 | 12/6/2017 2:34:46 PM | P | CANC |
|
|
Service inspection for MDP and MC Inspection requested via web by Debby Pierce Wrong permit requested, service is associated with entire building. Needed ELE16-04017
|
ELE16-04017
| Permanent Service | 12/6/2017 | 12/6/2017 | 12/6/2017 2:34:19 PM | P | FAIL |
|
|
110.24- Available fault current shall be posted prior to permenant service inspection. George will call with value, sticker on meter. 64k rated main breakers installed.
|
ELE17-02821
| Final | 12/5/2017 | 12/6/2017 | 12/6/2017 12:40:39 PM | A | FAIL |
|
|
Ron Phone #: ###-#### 210.8- All 120 volt receptacle outlets located in unfinished basement areas shall have GFCI protection. Recept. to left of panel. 250.32- Seperate building grounding electrode system, underground metal water pipe shall be supplemented by additional rod or pipe as per 250.53(A)(2). As per conversation with 345 issue discussed on rough in and equipment ground and underground metal water pipe all required. Disregard supplemental at house panel. 300.4- NM cable where enters enclosure shall have abrasion protection. 12-2 back of service panel. 408.4- Label garage circuit.
|
ELE17-02493
| Final | 12/5/2017 | 12/6/2017 | 12/6/2017 11:21:40 AM | A | FAIL |
|
|
Key over garage man door Phone #: ###-#### Inspection requested via web by Emmet Bushman 110.3- Basement bar GFCI will not hold. 680.11- Underground wiring shall not be installed under hot tub. Feed from garage service to sub fed house under hot tub.
|
ELE16-03933
| Electrical Rough-In | 12/5/2017 | 12/6/2017 | 12/6/2017 10:08:59 AM | A | PASS |
|
|
kitchen walls, dropped ceilings live works 101-105 Phone #: ###-#### Inspection requested via web by Cathy Duchek 101 not ready, 102 thru 105 live works walls and drop lids rough in ok cover
|
ELE17-03957
| Electrical Rough-In | 12/5/2017 | 12/6/2017 | 12/6/2017 9:26:55 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Island wall rough in ok cover
|
ELE17-02732
| Electrical Rough-In | 12/5/2017 | 12/6/2017 | 12/6/2017 9:26:19 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Inspection request was for IT room grid. 314.29- HVAC unit located above grid in IT room blocksan existing access door to elevator shaft that has electrical boxes. HVAC unit shall be located so access door can be opened 90 degrees for access. 400.12- Flexible cords shall not be installed above grid. Sump pump power cord shall not pass thru or be installed above grid.
|
ELE17-01549
| Electrical Rough-In | 12/5/2017 | 12/6/2017 | 12/6/2017 8:48:49 AM | A | PASS |
|
|
Shane is the contact his cell no.is ###-####.Historic pole lights on Main Street. Phone #: ###-#### Inspection requested via web by Shawna Gates Request will need public works approval. Underground and pole bases for south west of parking garage entrance rough in ok cover.
|