BLD19-03898
| FIRE-Final Inspection | 2/25/2020 | 2/25/2020 | 2/25/2020 3:07:56 PM | P | PART |
|
|
A temporary for life safety is being given for 90 days. A final life safety can be given when the project related fire alarm permit is finaled.
Phone #: ###-#### Inspection requested via web by Nate Carriveau
|
FIR19-00883
| INSP-Final Inspection | 2/25/2020 | 2/25/2020 | 2/25/2020 3:06:52 PM | P | PART |
|
|
A temporary for this permit has been given for 90 days. To final this permit the new notification devices need to sync with the existing notification devices as per NFPA 72.
Contact is Dirk. Building has been tested and verified for synchronization. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD19-02982
| FIRE-Final Inspection | 2/25/2020 | 2/25/2020 | 2/25/2020 3:05:21 PM | P | PASS |
|
|
Life safety passed.
Jose Phone #: ###-####
|
BLD20-00103
| FIRE-Final Inspection | 2/25/2020 | 2/25/2020 | 2/25/2020 12:36:01 PM | P | PASS |
|
|
Life safety passed. The fire alarm system that had been installed without a permit has been removed.
Final inspection request. Phone #: ###-#### Inspection requested via web by Jason Richardson
|
FIR19-00770
| INSP-Sprinkler Rough-in/Hydro | 2/25/2020 | 2/25/2020 | 2/25/2020 12:18:32 PM | P | PASS |
|
|
Overhead hydro witnessed with no pressure loss.
Cole will be the contact. Please give him an hours notice to meet you there. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD20-00284
| FIRE-Final Inspection | 2/24/2020 | 2/25/2020 | 2/25/2020 11:57:55 AM | A | PASS |
|
|
Life safety passed.
call for access- Christina Phone #: ###-####
|
FIR19-00831
| INSP-Sprinkler Rough-in | 2/24/2020 | 2/25/2020 | 2/25/2020 10:32:40 AM | A | PASS |
|
|
Rough-in passed. Need to add one 4 way brace and possible additional branchline bracing as discussed. No piping to be covered until additional rough-in inspection has been scheduled.
Johnathon Phone #: ###-####
|
FIR19-00816
| INSP-Sprinkler Rough-in | 2/24/2020 | 2/25/2020 | 2/25/2020 10:02:39 AM | A | PASS |
|
|
Rough-in and tenting passed for the south half of tower 3. Piping is ok for cover. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD20-00443
| FIRE-Final Inspection | 2/24/2020 | 2/25/2020 | 2/25/2020 7:49:32 AM | A | PASS |
|
|
life safety passed.
Matt Phone #: ###-####
|