ELE17-03734
| Conference | 2/28/2018 | 2/28/2018 | 2/28/2018 4:50:55 PM | P | DONE |
|
|
Discussed stairway to alley lighting and sump room. On stairway to alley the lighting has been removed for stairway and shall be reinstalled asap as this path is being used daily. Sump pump room will be used as a spray down room. A pressure washer will be present in room. Room shall be concidered a wet location.
|
ELE18-00278
| Electrical Rough-In | 2/28/2018 | 2/28/2018 | 2/28/2018 4:40:43 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Except 1421 rest of grid rough in ok cover
|
ELE17-03734
| Electrical Rough-In | 2/28/2018 | 2/28/2018 | 2/28/2018 4:29:25 PM | P | PASS |
|
|
We are requesting a wall rough-in in the basement area for this afternoon. Our contact is Luke @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Prep kitchen #2 to right of door walls and hard lid rough in ok cover
|
ELE17-04019
| Final | 2/28/2018 | 2/28/2018 | 2/28/2018 4:27:41 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kevin Burke BCC 4 05 32- No code violation to be retained. 314.25- All boxes shall have covers installed. Several recessed lighting with junction box covers not installed.
|
ELE18-00727
| Electrical Rough-In | 2/27/2018 | 2/28/2018 | 2/28/2018 3:00:21 PM | P | PASS |
|
|
Ufer Phone #: ###-#### Inspection requested via web by Tom Jenkins Concrete encased electrode rough in ok cover
|
ELE18-00727
| Electrical Rough-In | 2/28/2018 | 2/28/2018 | 2/28/2018 2:59:43 PM | P | FAIL |
|
|
Ufer Phone #: ###-#### Inspection requested via web by Tom Jenkins 590.6(B)- Receptacles other than 120 volt used for temp power shall have GFCI protection. 30 amp spider box.
|
ELE17-04117
| Electrical Rough-In | 2/28/2018 | 2/28/2018 | 2/28/2018 2:45:34 PM | P | PASS |
|
|
Please contact Matt Bruns with any questions
Thank you! Phone #: ###-#### Inspection requested via web by JENNY EMEL Offices 312, 313, 314, 315, conference rm 316, reception 322, admin 323, 324, work rm 325 and break rm door 326 B wall rough in ok cover
|
ELE16-03933
| Final | 2/28/2018 | 2/28/2018 | 2/28/2018 2:26:37 PM | P | PASS |
|
|
Final on all live work Units 101, 102, 103, 104, 105 Early afternoon preferred Contact Bob Mott Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek All complete, signed off in office. Final ok
|
ELE16-03932
| Final | 2/28/2018 | 2/28/2018 | 2/28/2018 2:26:37 PM | P | PASS |
|
|
All complete, signed off in office. Final ok
|
ELE16-03931
| Final | 2/28/2018 | 2/28/2018 | 2/28/2018 2:24:02 PM | P | PASS |
|
|
All complete, signed off in office. Final ok
|
ELE16-00580
| Final | 2/28/2018 | 2/28/2018 | 2/28/2018 2:23:17 PM | P | PASS |
|
|
All complete, signed off in office. Final ok
|
ELE18-00352
| Permanent Service | 2/27/2018 | 2/28/2018 | 2/28/2018 12:33:10 PM | A | FAIL |
|
|
Please inspect the meter base on the left. Phone #: ###-#### Inspection requested via web by Ryan Wilson 110.9- Equipment intended to interupt current at fault levels shall have an interupting rating at least equal to the current that is available at the line terminals of the equipment. 12,081 available and 10k rated main breakers.
|
ELE17-04081
| Electrical Rough-In | 2/27/2018 | 2/28/2018 | 2/28/2018 11:59:57 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mark M EMU monitoring room ceiling grid rough in ok cover
|
ELE18-00763
| Rough-In Permanent Service | 2/27/2018 | 2/28/2018 | 2/28/2018 11:26:04 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt 110.3- As per manufacturers instructions furnace shall have a minimum of 12 ga branch circuit. 210.52(A)(2)- Cabinet spec not found. Possible wall space each side of fireplace. 210.52(C)(1)- If receptacle located in pantry serve counter top space no point on counter shall be more than 24" from a receptacle. 300.15- Master bath stool fan not made up. 300.3- 600 volt and class 2 in same box for floor heat. Both shall have rating to cover voltage present in box. 408.3(A)(2)- Service conductor terminations shall have barriers installed. * Meter load terminations shall be lower lugs. Upper for incoming conductors.
|
ELE18-00220
| Electrical Rough-In | 2/27/2018 | 2/28/2018 | 2/28/2018 10:23:38 AM | A | PASS |
|
|
Bigger Remodel than started with. Finally got rough-in. They will be remodeling all of the downstairs and garage do to a flood caused by broken water pipe. There will be another rough-in on the down stairs remodel later. Phone #: ###-#### Inspection requested via web by Kurtis Boller Fire barriers for out entry cans not complete. Stairway not ready. Full remodel, upstairs only rough in ok cover
|
ELE18-00494
| Rough-In Permanent Service | 2/27/2018 | 2/28/2018 | 2/28/2018 9:57:40 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|
ELE18-00353
| Rough-In Permanent Service | 2/27/2018 | 2/28/2018 | 2/28/2018 9:28:59 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|
ELE18-00755
| Temporary Service | 2/27/2018 | 2/28/2018 | 2/28/2018 9:05:07 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE18-00756
| Temporary Service | 2/27/2018 | 2/28/2018 | 2/28/2018 9:04:38 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE17-01982
| Final | 2/26/2018 | 2/28/2018 | 2/27/2018 2:31:59 PM | A | PASS |
|
|
Install 2 park signs 1 in alley way and one on corner of alley and Myrtle. Install 1 sidewalk sign on Capitol. All Primary Power by Others Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok
|
ELE17-01982
| Electrical Rough-In | 2/26/2018 | 2/28/2018 | 2/27/2018 2:30:44 PM | A | PASS |
|
|
Install 2 park signs 1 in alley way and one on corner of alley and Myrtle. Install 1 sidewalk sign on Capitol. All Primary Power by Others Phone #: ###-#### Inspection requested via web by Ken Olsen Listing and disconnecting means confirmed rough in ok
|