Inspections for the day of: Wednesday, February 28, 2018.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03734 Conference2/28/20182/28/20182/28/2018 4:50:55 PMPDONE
Discussed stairway to alley lighting and sump room.
On stairway to alley the lighting has been removed for stairway and shall be reinstalled asap as this path is being used daily.
Sump pump room will be used as a spray down room. A pressure washer will be present in room. Room shall be concidered a wet location.
ELE18-00278 Electrical Rough-In2/28/20182/28/20182/28/2018 4:40:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Except 1421 rest of grid rough in ok cover
ELE17-03734 Electrical Rough-In2/28/20182/28/20182/28/2018 4:29:25 PMPPASS
We are requesting a wall rough-in in the basement area for this afternoon. Our contact is Luke @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Prep kitchen #2 to right of door walls and hard lid rough in ok cover
ELE17-04019 Final2/28/20182/28/20182/28/2018 4:27:41 PMPFAIL
Phone #: ###-#### Inspection requested via web by Kevin Burke
BCC 4 05 32- No code violation to be retained.
314.25- All boxes shall have covers installed. Several recessed lighting with junction box covers not installed.
ELE18-00727 Electrical Rough-In2/27/20182/28/20182/28/2018 3:00:21 PMPPASS
Ufer Phone #: ###-#### Inspection requested via web by Tom Jenkins
Concrete encased electrode rough in ok cover
ELE18-00727 Electrical Rough-In2/28/20182/28/20182/28/2018 2:59:43 PMPFAIL
Ufer Phone #: ###-#### Inspection requested via web by Tom Jenkins
590.6(B)- Receptacles other than 120 volt used for temp power shall have GFCI protection. 30 amp spider box.
ELE17-04117 Electrical Rough-In2/28/20182/28/20182/28/2018 2:45:34 PMPPASS
Please contact Matt Bruns with any questions

Thank you! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Offices 312, 313, 314, 315, conference rm 316, reception 322, admin 323, 324, work rm 325 and break rm door 326 B wall rough in ok cover
ELE16-03933 Final2/28/20182/28/20182/28/2018 2:26:37 PMPPASS
Final on all live work Units 101, 102, 103, 104, 105
Early afternoon preferred
Contact Bob Mott
Thank you
Phone #: ###-#### Inspection requested via web by Cathy Duchek
All complete, signed off in office. Final ok
ELE16-03932 Final2/28/20182/28/20182/28/2018 2:26:37 PMPPASS
All complete, signed off in office. Final ok
ELE16-03931 Final2/28/20182/28/20182/28/2018 2:24:02 PMPPASS
All complete, signed off in office. Final ok
ELE16-00580 Final2/28/20182/28/20182/28/2018 2:23:17 PMPPASS
All complete, signed off in office. Final ok
ELE18-00352 Permanent Service2/27/20182/28/20182/28/2018 12:33:10 PMAFAIL
Please inspect the meter base on the left. Phone #: ###-#### Inspection requested via web by Ryan Wilson
110.9- Equipment intended to interupt current at fault levels shall have an interupting rating at least equal to the current that is available at the line terminals of the equipment. 12,081 available and 10k rated main breakers.
ELE17-04081 Electrical Rough-In2/27/20182/28/20182/28/2018 11:59:57 AMAPASS
Phone #: ###-#### Inspection requested via web by Mark M
EMU monitoring room ceiling grid rough in ok cover
ELE18-00763 Rough-In Permanent Service2/27/20182/28/20182/28/2018 11:26:04 AMAFAIL
Phone #: ###-#### Inspection requested via web by John VanZandt
110.3- As per manufacturers instructions furnace shall have a minimum of 12 ga branch circuit.
210.52(A)(2)- Cabinet spec not found. Possible wall space each side of fireplace.
210.52(C)(1)- If receptacle located in pantry serve counter top space no point on counter shall be more than 24" from a receptacle.
300.15- Master bath stool fan not made up.
300.3- 600 volt and class 2 in same box for floor heat. Both shall have rating to cover voltage present in box.
408.3(A)(2)- Service conductor terminations shall have barriers installed.
* Meter load terminations shall be lower lugs. Upper for incoming conductors.
ELE18-00220 Electrical Rough-In2/27/20182/28/20182/28/2018 10:23:38 AMAPASS
Bigger Remodel than started with. Finally got rough-in. They will be remodeling all of the downstairs and garage do to a flood caused by broken water pipe. There will be another rough-in on the down stairs remodel later. Phone #: ###-#### Inspection requested via web by Kurtis Boller
Fire barriers for out entry cans not complete. Stairway not ready. Full remodel, upstairs only rough in ok cover
ELE18-00494 Rough-In Permanent Service2/27/20182/28/20182/28/2018 9:57:40 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok
ELE18-00353 Rough-In Permanent Service2/27/20182/28/20182/28/2018 9:28:59 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok
ELE18-00755 Temporary Service2/27/20182/28/20182/28/2018 9:05:07 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE18-00756 Temporary Service2/27/20182/28/20182/28/2018 9:04:38 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE17-01982 Final2/26/20182/28/20182/27/2018 2:31:59 PMAPASS
Install 2 park signs 1 in alley way and one on corner of alley and Myrtle. Install 1 sidewalk sign on Capitol. All Primary Power by Others Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok
ELE17-01982 Electrical Rough-In2/26/20182/28/20182/27/2018 2:30:44 PMAPASS
Install 2 park signs 1 in alley way and one on corner of alley and Myrtle. Install 1 sidewalk sign on Capitol. All Primary Power by Others Phone #: ###-#### Inspection requested via web by Ken Olsen Listing and disconnecting means confirmed rough in ok