ELE17-01386
| ELE-Aging Inspection | 2/3/2020 | 2/3/2020 | 2/5/2020 11:10:21 AM | | DONE |
|
|
No activity on permit. Contractor is aware of the need to final aging permits.
|
ELE19-03595
| Electrical Rough-In | 1/28/2020 | 2/3/2020 | 2/3/2020 2:11:02 PM | P | CANC |
|
|
Inspection to reconnect power Phone #: ###-#### Inspection requested via web by BRS Permitting
|
ELE19-03595
| Permanent Service | 2/3/2020 | 2/3/2020 | 2/3/2020 2:07:51 PM | P | FAIL |
|
|
Inspection to reconnect power Phone #: ###-#### Inspection requested via web by BRS Permitting Discription doesnt match job. Meter is in place No reconnection needed. No answer at contact number
|
ELE20-00307
| Electrical Rough-In | 2/3/2020 | 2/3/2020 | 2/3/2020 1:53:24 PM | P | NH |
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley
|
ELE19-02932
| Final | 2/3/2020 | 2/3/2020 | 2/3/2020 1:52:07 PM | P | PASS |
|
|
garage code 1905 Phone #: ###-#### Inspection requested via web by kevin blackmon corrections made final ok
|
ELE20-00388
| Temporary Service | 2/2/2020 | 2/3/2020 | 2/3/2020 1:34:48 PM | P | PASS |
|
|
greetings looking for an ok to energize temp power pole any issues or questions please call thank you have a great day Phone #: ###-#### Inspection requested via web by leon ramirez t/s u/g n ok
|
ELE19-04947
| Electrical Rough-In | 2/3/2020 | 2/3/2020 | 2/3/2020 1:06:07 PM | P | PEND |
|
|
bracing has been done Phone #: ###-#### Inspection requested via web by dennis mcneely Wire running through holes in trusses have been moved and truss repair has ben done. Electrical rough in ok pending building inspection
|
ELE20-00027
| Electrical Rough-In | 2/3/2020 | 2/3/2020 | 2/3/2020 1:05:42 PM | P | PEND |
|
|
bracing has been done Phone #: ###-#### Inspection requested via web by dennis mcneely Wire running through holes in trusses have been moved and truss repair has ben done. Electrical rough in ok pending building inspection
|
ELE19-04158
| Final | 2/3/2020 | 2/3/2020 | 2/3/2020 12:29:53 PM | P | PASS |
|
|
garage code 7750, key for house inside exterior outlet by front door Phone #: ###-#### Inspection requested via web by Robert Schroder Corrections made Final ok
|
ELE20-00353
| Final | 2/2/2020 | 2/3/2020 | 2/3/2020 10:37:24 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Dave Brueggemann 300.5 Conduits shall be burried 18in deep. 356.12(1) LFMC shall not be used where exposed to physical damage.
|
ELE20-00214
| Temporary Service | 1/31/2020 | 2/3/2020 | 2/3/2020 10:33:30 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE20-00188
| Final | 1/31/2020 | 2/3/2020 | 2/3/2020 9:41:12 AM | A | FAIL |
|
|
Please inspect is there As early as possible please call ###-#### so he can arrive and open the door if needed Phone #: ###-#### Inspection requested via web by shane miller 440.22C Overcurrent shall not exceed manufacturer ratings. (25A max 30A installed Minnimum circuit ampacity is 23.8A. 25A breaker or fuses must be installed)
|
ELE20-00280
| Rough-In Permanent Service | 2/3/2020 | 2/3/2020 | 2/3/2020 9:35:27 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard rough in ok p/s u/g n ok
|
ELE19-04791
| Electrical Rough-In | 1/30/2020 | 2/3/2020 | 2/3/2020 8:42:51 AM | A | PASS |
|
|
Ron. Secondary contact Nick ###-#### Phone #: ###-#### center wall only ok to cover
|
ELE19-00964
| Final | 1/31/2020 | 2/3/2020 | 2/3/2020 8:03:40 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by chris hopkins...rescheduled do to time constraints and lack of inspectors Final ok
|
ELE19-00964
| Electrical Rough-In | 2/3/2020 | 2/3/2020 | 2/3/2020 8:03:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by chris hopkins...rescheduled do to time constraints and lack of inspectors Rough in ok
|