BLD16-04166
| FIRE-Final Inspection | 2/8/2018 | 2/9/2018 | 2/9/2018 2:58:10 PM | A | PASS |
|
|
Life safety passed
Phone #: ###-#### Inspection requested via web by Brett Barrier
|
FIR17-00446
| INSP-Sprinkler Rough-in | 2/8/2018 | 2/9/2018 | 2/9/2018 12:47:06 PM | P | PASS |
|
|
Tenting and piping rough-in passed. Piping can be covered.
|
FIR17-00709
| INSP-Final Inspection | 2/8/2018 | 2/9/2018 | 2/9/2018 12:46:31 PM | A | PASS |
|
|
Permit finaled
Jessica Phone #: ###-####
|
FIR16-00628
| INSP-Final Inspection | 2/7/2018 | 2/9/2018 | 2/9/2018 10:23:05 AM | A | FAIL |
|
|
Plan modifications are needed for all of the changes required. There are many locations where strobes are over spaced including the Common Areas and in the Sleeping Rooms. Panels have been relocated. Smoke detectors for door release need to be centered on the door and with-in 5'-0" of the door and more than 3'-0" from air diffusers. Strobes need to be added in acouple locations.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR17-00705
| INSP-Final Inspection | 2/8/2018 | 2/9/2018 | 2/9/2018 10:14:23 AM | A | CANC |
|
|
Could not perform testing due to fire alrm issues.
Dave Phone #: ###-####
|
FIR16-00821
| INSP-Final Inspection | 2/8/2018 | 2/9/2018 | 2/9/2018 10:12:35 AM | A | PART |
|
|
Could not final due to fire alrm issues. We did however perform the forward flush test which passed.
|
BLD17-03725
| FIRE-Final Inspection | 2/7/2018 | 2/9/2018 | 2/9/2018 9:56:23 AM | A | FAIL |
|
|
Provide panic hardware at the Seating Area exit door as per plans, provide occupant load sign, repair exit signs and emergency lights/exit discharge lights, mount the fire extinguisher, provide ADA hardware on the back Storage Room door.
|