Inspections for the day of: Friday, February 9, 2018.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-04166 FIRE-Final Inspection2/8/20182/9/20182/9/2018 2:58:10 PMAPASS
Life safety passed

Phone #: ###-#### Inspection requested via web by Brett Barrier
FIR17-00446 INSP-Sprinkler Rough-in2/8/20182/9/20182/9/2018 12:47:06 PMPPASS
Tenting and piping rough-in passed. Piping can be covered.
FIR17-00709 INSP-Final Inspection2/8/20182/9/20182/9/2018 12:46:31 PMAPASS
Permit finaled

Jessica Phone #: ###-####
FIR16-00628 INSP-Final Inspection2/7/20182/9/20182/9/2018 10:23:05 AMAFAIL
Plan modifications are needed for all of the changes required. There are many locations where strobes are over spaced including the Common Areas and in the Sleeping Rooms. Panels have been relocated. Smoke detectors for door release need to be centered on the door and with-in 5'-0" of the door and more than 3'-0" from air diffusers. Strobes need to be added in acouple locations.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR17-00705 INSP-Final Inspection2/8/20182/9/20182/9/2018 10:14:23 AMACANC
Could not perform testing due to fire alrm issues.

Dave Phone #: ###-####
FIR16-00821 INSP-Final Inspection2/8/20182/9/20182/9/2018 10:12:35 AMAPART
Could not final due to fire alrm issues. We did however perform the forward flush test which passed.
BLD17-03725 FIRE-Final Inspection2/7/20182/9/20182/9/2018 9:56:23 AMAFAIL
Provide panic hardware at the Seating Area exit door as per plans, provide occupant load sign, repair exit signs and emergency lights/exit discharge lights, mount the fire extinguisher, provide ADA hardware on the back Storage Room door.