Inspections for the day of: Monday, March 17, 2014.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-00244 ELE-Aging Inspection3/17/20143/17/20143/19/2014 4:10:34 PM DONE
spoke with justin and hes looking into it
ELE12-01787 ELE-Aging Inspection3/17/20143/17/20143/19/2014 4:03:19 PM DONE
not ready for final waiting on trim
ELE11-02529 ELE-Aging Inspection3/17/20143/17/20143/19/2014 3:59:39 PM DONE
left message
ELE12-01337 ELE-Aging Inspection3/17/20143/17/20143/19/2014 3:57:00 PM DONE
spoke with nathan and he will call it in
ELE14-00627 Final3/17/20143/17/20143/17/2014 3:28:10 PMPDONE
We will call for inspection when ready. thanks! Phone #: ###-#### >> Inspection requested via web by Kendra Lanham needed perm. service
ELE14-00627 Permanent Service3/17/20143/17/20143/17/2014 3:27:30 PMPPASS
We will call for inspection when ready. thanks! Phone #: ###-#### >> Inspection requested via web by Kendra Lanham p/s o/h rec ok Need 2nd ground rod after fallen tree limbs are moved.
ELE14-00621 Electrical Rough-In3/17/20143/17/20143/17/2014 3:05:04 PMPPASS
I need a wall only inspection please. Phone #: ###-#### >> Inspection requested via web by Cindie Swaim roughin ok to cover on walls indicated on plans
ELE14-00533 Final3/16/20143/17/20143/17/2014 2:24:43 PMPPASS
call 15 minutes ahead so we can meet and have it open for inspection Phone #: ###-#### >> Inspection requested via web by Eddy Udry final ok service and interior wiring
ELE14-00616 Temporary Service3/14/20143/17/20143/17/2014 1:24:29 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Chris Chesnut t/s o/h n ok
GCE14-00019 GCE-Final3/14/20143/17/20143/17/2014 1:03:26 PMPPASS
Tom ###-#### please call 30 minutes before final ok corrections made
ELE14-00619 Conference3/14/20143/17/20143/17/2014 12:27:50 PMADONE
Andrie Phone #: ###-#### explain how to relocate bath plug.
ELE13-03146 Final3/14/20143/17/20143/17/2014 10:32:32 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Jerry Moore 300.5- conduit out to pool panel needs to be min. 18" to top of conduit on the east side of house. If this will be concrete covered then your ok. Could'nt find anyone on job to answer this question.
ELE14-00504 Electrical Rough-In3/14/20143/17/20143/17/2014 9:43:19 AMAPASS
Wall - Shane is onsite contact his cell no. is ###-#### Phone #: ###-#### >> Inspection requested via web by Mike Basye rough in ok to cover areas marked on plans 1st floor
ELE14-00475 Electrical Rough-In3/14/20143/17/20143/17/2014 9:22:08 AMAPASS
This is an underground inspection. Contact is Alan Krishnek. Phone #: ###-#### >> Inspection requested via web by Scott Campbell ok to cover u/g
ELE14-00602 Electrical Rough-In3/14/20143/17/20143/17/2014 8:54:37 AMAPASS
Contact: Jeremy Thornock Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough in conference room ceiling and wall ok
ELE14-00501 Electrical Rough-In3/17/20143/17/20143/17/2014 8:19:07 AMPCANC
Walls only please. >> Inspection requested via web by Cindie Swaim Inspection cancelled from web by: Cindie Swaim