Inspections for the day of: Tuesday, March 20, 2018.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00474 INSP-Sprinkler Rough-in3/20/20183/20/20183/20/2018 1:35:53 PMPPART
Todays inspection was just for the supply piping to the FDC that runs under the floor. The piping in itself is ok but the combustible concealed spaces on both side of the gym need to be addressed. I spoke to Tim Frost in plan review and he was going to follow up with the contractor. Piping can not be covered until this is resolved due to needing access to install additional piping , if required.

Mark Jensen is the contact for this rough-in for the FDC. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD17-03994 FIRE-Final Inspection3/19/20183/20/20183/20/2018 12:35:55 PMPFAIL
Provide annual inspection for the fire extinguishers, remove hardware from the Stockroom door, remove tape from the upright sprinkler heads in the Stockroom, call for fire sprinkler permit final

late as poss // Tommy Lyles Phone #: ###-####
BLD17-03569 FIRE-Final Inspection3/20/20183/20/20183/20/2018 12:34:24 PMPPASS
Life safety passed

Troy Phone #: ###-####
BLD17-02943 FIRE-Final Inspection3/20/20183/20/20183/20/2018 12:11:53 PMPCANC
No life safety sign off required per the project details


AS LATE AS POSSIBLE // Mark Phone #: ###-####
BLD18-00195 FIRE-Final Inspection3/20/20183/20/20183/20/2018 12:02:11 PMPCANC
No fire life safety sign off required per the project details.

call 15 mins ahead- Brian Phone #: ###-####
NAF17-00084 INSP-Final3/19/20183/20/20183/20/2018 10:09:40 AMAFAIL
The duct smoke detectors have no sample tubes installed. No testing performed.


John Howard - Technician Phone #: ###-#### Inspection requested via web by John Siewert
FIR17-00670 INSP-Sprinkler Rough-in3/19/20183/20/20183/20/2018 8:12:34 AMAPART
Provide flexible couplings on both sides of the CMU wall, provide sprinkler protection in small room as discussed, provide branchline restraints as shown on the plans, provide verification that the CC heads are listed for 9' off of walls. Provide all of the missing small documents

George Jess is the contact for this inspection. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus