FIR17-00474
| INSP-Sprinkler Rough-in | 3/20/2018 | 3/20/2018 | 3/20/2018 1:35:53 PM | P | PART |
|
|
Todays inspection was just for the supply piping to the FDC that runs under the floor. The piping in itself is ok but the combustible concealed spaces on both side of the gym need to be addressed. I spoke to Tim Frost in plan review and he was going to follow up with the contractor. Piping can not be covered until this is resolved due to needing access to install additional piping , if required.
Mark Jensen is the contact for this rough-in for the FDC. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD17-03994
| FIRE-Final Inspection | 3/19/2018 | 3/20/2018 | 3/20/2018 12:35:55 PM | P | FAIL |
|
|
Provide annual inspection for the fire extinguishers, remove hardware from the Stockroom door, remove tape from the upright sprinkler heads in the Stockroom, call for fire sprinkler permit final
late as poss // Tommy Lyles Phone #: ###-####
|
BLD17-03569
| FIRE-Final Inspection | 3/20/2018 | 3/20/2018 | 3/20/2018 12:34:24 PM | P | PASS |
|
|
Life safety passed
Troy Phone #: ###-####
|
BLD17-02943
| FIRE-Final Inspection | 3/20/2018 | 3/20/2018 | 3/20/2018 12:11:53 PM | P | CANC |
|
|
No life safety sign off required per the project details
AS LATE AS POSSIBLE // Mark Phone #: ###-####
|
BLD18-00195
| FIRE-Final Inspection | 3/20/2018 | 3/20/2018 | 3/20/2018 12:02:11 PM | P | CANC |
|
|
No fire life safety sign off required per the project details.
call 15 mins ahead- Brian Phone #: ###-####
|
NAF17-00084
| INSP-Final | 3/19/2018 | 3/20/2018 | 3/20/2018 10:09:40 AM | A | FAIL |
|
|
The duct smoke detectors have no sample tubes installed. No testing performed.
John Howard - Technician Phone #: ###-#### Inspection requested via web by John Siewert
|
FIR17-00670
| INSP-Sprinkler Rough-in | 3/19/2018 | 3/20/2018 | 3/20/2018 8:12:34 AM | A | PART |
|
|
Provide flexible couplings on both sides of the CMU wall, provide sprinkler protection in small room as discussed, provide branchline restraints as shown on the plans, provide verification that the CC heads are listed for 9' off of walls. Provide all of the missing small documents
George Jess is the contact for this inspection. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|