Inspections for the day of: Thursday, March 7, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00717 Final3/5/20193/7/20193/7/2019 2:09:22 PMACANC
Please contact electrician Mick @ ###-#### prior to inspection to have him meet you at location to go over what was completed. There was some confusion whether or not this was a state or city permit so this inspection was not resolved sooner. Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON
Need to verify if state or city owned permit for inspections, work space clearences not met with concrete support in front of main breaker in generator
ELE19-00738 Electrical Rough-In3/7/20193/7/20193/7/2019 1:59:56 PMPPASS
Wall rough in Phone #: ###-#### Inspection requested via web by kendall bender
Wall with future power for projector on south side half wall ok to cover
ELE16-03000 Conference3/7/20193/7/20193/7/2019 1:49:38 PMPDONE
Nick Phone #: ###-####
Needed extension and will clone it
ELE16-03000 ELE-Request for Extension3/7/20193/7/20193/7/2019 1:49:29 PMPPASS
Nick Phone #: ###-####
Granted 180 day extension
ELE19-00678 Rough-In Permanent Service3/5/20193/7/20193/7/2019 1:46:44 PMPFAIL
Phone #: ###-#### Inspection requested via web by shane miller
Metering device required
ELE19-00203 Final3/6/20193/7/20193/7/2019 1:21:44 PMAFAIL
Please call number above for fence and gear lock codes or call ###-#### Phone #: ###-#### Inspection requested via web by Kevin Perez
Available fault current calc required
GF performance test required for 480v 1000 amp systems
ELE19-00641 Electrical Rough-In3/6/20193/7/20193/7/2019 12:46:55 PMAPASS
Inspection for Bonding, Under ground and Water Bonding Any questions please call Louis at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller
u/g and bonding of 4 corners and light,diving board,cover,and back to equipment ok to cover
ELE18-03385 Electrical Rough-In3/7/20193/7/20193/7/2019 11:16:35 AMAPASS
Rough in for cover in building J breezeway''s and rise room.
Contact Scott Wilson.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Brrezeway and riser room ok to cover
ELE18-03978 Final3/6/20193/7/20193/7/2019 11:03:19 AMAPASS
This project should have been finaled when it passed inspection for permanent service for panel fire. Please call with any questions.

Thank you ; have a nice day! Karin ###-#### Phone #: ###-#### Inspection requested via web by JENNY EMEL
Final ok