ELE19-00913
| Final | 5/1/2019 | 5/1/2019 | 5/1/2019 1:55:30 PM | P | PART |
|
|
Jake Phone #: ###-#### Basement and entrances to stairs only. Level 1 all is safe. Boxes will only be open while work is being performed. TCO for area noted OK
|
ELE19-00652
| Final | 4/30/2019 | 5/1/2019 | 5/1/2019 1:33:32 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Final ok
|
ELE19-00288
| Final | 4/30/2019 | 5/1/2019 | 5/1/2019 11:43:28 AM | A | FAIL |
|
|
Contact is Neil Adams @ ###-#### Phone #: ###-#### Inspection requested via web by Todd Alder 110.26(A)(4)- Disconnect door shall open to a minimum of 90 degrees. Disconnect located in office. Move or remove. 210.63- A receptacle outlet shall be located with in 25' of AC unit. 314.29- Covers for conduit bodies shall be accessible with out damage to wall finish. LB located to right of main disconnect. 406.5- Receptacle outlets shall be securely mounted in place. Single receptacle mezz. 440.6- AC overcurrent protection shall not exceed value noted on nameplate. 50 amp installed 40 amp max. BCC4 05-32- Code violation not to be retained.
|
ELE19-01334
| Final | 4/30/2019 | 5/1/2019 | 5/1/2019 10:47:23 AM | A | PASS |
|
|
Pls contact Bryce (Foreman) @ ###-#### or George (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes Final ok
|
ELE18-01608
| Final | 4/30/2019 | 5/1/2019 | 5/1/2019 10:08:31 AM | A | PART |
|
|
Inspection for baboon occupancy... Phone #: ###-#### Inspection requested via web by Mike McCarrel No general public shall have access, only baboon keepers will have access to baboon areas only. Electrical contractor keeps each panel board locked. TCO EO Wilson bldg baboon areas only ok
|