Inspections for the day of: Thursday, May 17, 2018.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-03496 FIRE-Final Inspection5/17/20185/17/20185/17/2018 3:15:10 PMPFAIL
Provide occupant load sign, provide testing/annunciator for the duct smoke detector, provide approval of the kitchen hood/appliance layout from the mechanical inspector.

Phone #: ###-#### Inspection requested via web by kevin debelloy
FIR18-00408 INSP-Sprinkler Rough-in5/17/20185/17/20185/17/2018 2:26:23 PMPPASS
The In Building Riser is ok for cover. No other piping installed yet.


Bryan Collins is the contact for this underground rough-in inspection. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00321 INSP-Final Inspection5/16/20185/17/20185/17/2018 2:25:30 PMPFAIL
Need legible drawings/prints, need mechanical inspectors approval of the hood/appliance lay out prior to a final sign off.

Dave Phone #: ###-####
BLD17-00959 FIRE-Final Inspection5/17/20185/17/20185/17/2018 2:16:40 PMPPART
Sleep room and lactation room life safety passed
FIR18-00114 INSP-Final Inspection5/16/20185/17/20185/17/2018 11:11:47 AMAPASS
Permit finaled


AM inspection - contact Rafe Barrett for JCI rep Phone #: ###-#### Inspection requested via web by Shane Lesteberg
FIR17-00454 INSP-Final Inspection5/15/20185/17/20185/17/2018 10:46:47 AMAFAIL
Display was not set up, I called mike when I was back in the area but could only leave a message. Will need to reschedule.


First thing in the morning if possible thanks. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00485 INSP-Final Inspection5/15/20185/17/20185/17/2018 10:46:29 AMAFAIL
Display was not set up, I called mike when I was back in the area but could only leave a message. Will need to reschedule.

First thing in the morning if possible thanks. Phone #: ###-#### Inspection requested via web by Sam Ball
BLD18-00840 FIRE-Final Inspection5/15/20185/17/20185/17/2018 10:39:31 AMAPASS
Life safety passed

Please call ahead for access - Ovilia Phone #: ###-####
BLD18-01041 FIRE-Final Inspection5/16/20185/17/20185/17/2018 10:22:24 AMAFAIL
Provide address, provide revised floor plan showing the removal of the wall and cooler, repair the non-functional exit signs/emergency lights or remove the non-required/non-functional ones, install ceiling tile, provide automatic flush bolts or get plan review approval to delete in-active leaf of door, mount and tag the fire extinguisher


Chuck Phone #: ###-####
FIR17-00445 INSP-Final Inspection5/15/20185/17/20185/17/2018 7:58:17 AMAPASS
Permit finaled


First thing in the morning if possible thanks. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00476 INSP-Final Inspection5/15/20185/17/20185/17/2018 7:57:53 AMAPASS
Permit finaled

First thing in the morning if possible thanks. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00456 INSP-Final Inspection5/15/20185/17/20185/17/2018 7:57:23 AMAPASS
Permit finaled


First thing in the morning if possible thanks. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00487 INSP-Final Inspection5/15/20185/17/20185/17/2018 7:56:59 AMAPASS
Permit finaled

First thing in the morning if possible thanks. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00462 INSP-Final Inspection5/15/20185/17/20185/17/2018 7:56:31 AMAPASS
Permit finaled

First thing in the morning if possible thanks. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00494 INSP-Final Inspection5/15/20185/17/20185/17/2018 7:55:56 AMAPASS
Permit finaled

First thing in the morning if possible thanks. Phone #: ###-#### Inspection requested via web by Sam Ball
BLD13-02973 FIRE-Final Inspection5/16/20185/17/20185/17/2018 12:00:00 AMACANC
Jesse Phone #: ###-####