Inspections for the day of: Friday, May 24, 2019.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00070 ELE-Aging Inspection5/24/20195/24/20195/24/2019 3:22:31 PM FAIL
Waiting on contractor to respond
ELE19-01903 Permanent Service5/23/20195/24/20195/24/2019 3:12:36 PMPFAIL
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
110.24- Available fault current shall be posted prior to permenant service inspection.
Had verbal with wireman
ELE19-01872 Final5/23/20195/24/20195/24/2019 2:34:59 PMPFAIL
Phone #: ###-#### Inspection requested via web by Tricia Henderson
No one home. Must include description of work performed. Will not search to locate item added.
ELE19-00374 Rough-In Permanent Service5/24/20195/24/20195/24/2019 2:14:16 PMPPASS
Tom Phone #: ###-####
Underground to service not connected to service. Rough in ok cover p/s u/g n ok
ELE18-04603 Rough-In Permanent Service5/24/20195/24/20195/24/2019 2:13:01 PMPPASS
Tom Phone #: ###-####
Underground to service not connected to service. Garage rough in ok cover p/s u/g n ok
ELE19-01927 Electrical Rough-In5/24/20195/24/20195/24/2019 1:49:51 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Underslab rough in ok cover
ELE19-01483 Final5/21/20195/24/20195/24/2019 1:13:38 PMPNR
Please call ahead Phone #: ###-#### Inspection requested via web by Kyle Dillon
Metermain relocated to ground level. Will recall when grounds and neutrals seperation complete in panel. No other alterations allowed in this panel.
ELE19-01483 Rough-In Permanent Service5/21/20195/24/20195/24/2019 1:11:15 PMAPASS
Please call ahead Phone #: ###-#### Inspection requested via web by Kyle Dillon
p/s o/h rec ok
ELE19-00619 Final5/24/20195/24/20195/24/2019 12:56:22 PMPPASS
or all ###-#### Phone #: ###-#### Inspection requested via web by Robert Murray Final ok
ELE19-00962 Final5/24/20195/24/20195/24/2019 12:42:57 PMPPASS
Phone #: ###-#### Inspection requested via web by Neal Rumsey Final ok
ELE19-01847 Final5/24/20195/24/20195/24/2019 12:05:21 PMPPASS
Final inspection in conjunction with Old Dominion Solar

Thank you and have a wonderful long weekend! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Final ok
ELE19-01782 Final5/24/20195/24/20195/24/2019 11:59:02 AMAPASS
Please Call before Inspection Phone #: ###-#### Inspection requested via web by Matt Oranday Final ok
ELE19-00482 Final5/24/20195/24/20195/24/2019 11:23:53 AMAFAIL
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
110.3- Devices shall be installed as per instructions. Up short hall 3-way not working.
210.12- Level 1 office or bedroom shall have AFCI protection. Clothes rod present.
210.8- GFCI device shall be located in a readily accessible location not behind or inder tub deck. * Ensure access operational for jetted tub motor.
* Small garage door not working. No access to check receptacle
ELE19-00875 Final5/24/20195/24/20195/24/2019 10:19:10 AMAFAIL
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
314.25- Buried recessed can hall out guest bedroom.
410.16- Guest closet shall have completely enclosed lamps. Globe missing.
ELE19-01656 Electrical Rough-In5/23/20195/24/20195/24/2019 9:42:38 AMAFAIL
Soffit inspection Phone #: ###-#### Inspection requested via web by Ryan Wake
110.3- Soffit can fire hoods shall be installed as per manufacturers instructions. Only small openings are prmitted for entrance of conductors. Hoods are split from soffit to roof.
ELE19-01018 Electrical Rough-In5/23/20195/24/20195/24/2019 9:08:30 AMAPASS
walls Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Perimeter shell walls rough in ok cover
ELE19-00962 Conference5/24/20195/24/20195/24/2019 8:19:52 AMAFAIL
code 3484 Phone #: ###-#### Inspection requested via web by Neal Rumsey
Needed final inspection. Corrections not complete, refer still reverse polarity. Recall
ELE19-01825 Temporary Service5/23/20195/24/20195/24/2019 7:34:48 AMACANC
Jake is the contact Phone #: ###-#### >> Inspection requested via web by Deb Ipsen Inspection cancelled from web by: Deb Ipsen