Inspections for the day of: Thursday, May 25, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00031 FIR-Aging Inspection5/25/20175/25/20176/1/2017 8:20:49 AM DONE
I called ADT and Tyco and neither one can find an account for Macys and do not know what I'm talking about.
BLD17-01519 FIRE-Conference5/25/20175/25/20175/25/2017 11:40:38 AMPDONE
I met the property manager and pointed out the two locations of overspaced pendant heads and actually found a third over the sales floor.
FIR16-00557 INSP-Final Inspection5/24/20175/25/20175/25/2017 10:58:19 AMACANC
Mark Jensen is the contact for this final inspection. Thank you. Phone #: ###-#### Inspection requested via web by Kay Haney
FIR16-00406 INSP-Final Inspection5/24/20175/25/20175/25/2017 10:58:10 AMAPASS
permit finaled
FIR17-00082 INSP-Sprinkler Rough-in5/24/20175/25/20175/25/2017 10:57:46 AMAPASS
Underground supply piping is ok to cover
BLD16-02273 FIRE-Final Inspection5/24/20175/25/20175/25/2017 9:12:57 AMAPASS
Life safety passed. I noted that the self illuminating exit signs 20 year life span expires this month. The contact is going to purchase new lights asap.
BLD16-02650 FIRE-Final Inspection5/24/20175/25/20175/25/2017 8:06:22 AMAFAIL
Need fire alarm and fire sprinkler permits addressed. Need building address and apartment numbers, need fire extinguishers, need riser room signage. Smoke alarms tested ok.
FIR17-00192 INSP-Final Inspection5/23/20175/25/20175/25/2017 8:05:08 AMAFAIL
Net con was at a 6. Could not test flow switches due to fire sprinkler contractor not being present.
FIR16-00824 INSP-Final Inspection5/23/20175/25/20175/25/2017 8:04:12 AMAFAIL
Two concealer heads are located too far from ceiling, two sidewall heads have the shipping clips on them. Flow switches have not been pre-tested. Flow switches do not have covers installed
FIR16-00781 INSP-Final Inspection5/23/20175/25/20175/25/2017 8:02:24 AMAPASS
permit finaled