Inspections for the day of: Wednesday, May 30, 2018.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF18-00049 INSP-Sprinkler Rough-in/Hydro5/29/20185/30/20185/31/2018 3:01:13 PMPCANC
Not ready for an inspection or hydro test yet. I noted non-rated wood being used which is creating combustible concealed spaces that do not have sprinkler protection.


Call prior to going Phone #: 2085611337 >> Inspection requested via mobile web by Gabe
FIR12-00474 FIR-Aging Inspection5/30/20185/30/20185/31/2018 2:20:36 PM PASS
BLD17-02414 FIRE-Final Inspection5/30/20185/30/20185/30/2018 2:51:54 PMPFAIL
Missing ceiling in unit 102 closet.


Phone #: ###-#### Inspection requested via web by David Scaggs
FIR18-00141 INSP-Sprinkler Rough-in/Hydro5/30/20185/30/20185/30/2018 2:08:56 PMPPASS
The hydro test for the FDC passed.

Colton Cox is the contact for this FDC Hydro inspection. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD17-02429 FIRE-Final Inspection5/30/20185/30/20185/30/2018 1:57:42 PMPPASS
Life safety passed

Phone #: ###-#### Inspection requested via web by David Scaggs
FIR16-00708 INSP-Final Inspection5/25/20185/30/20185/30/2018 12:46:37 PMAFAIL
Partial inspection today. See entry by Lee for items tested today.

Nick Tank, inspecting technician, building is open access Phone #: ###-#### Inspection requested via web by Rose Peterson
BLD17-02015 FIRE-Final Inspection5/29/20185/30/20185/30/2018 11:00:15 AMAFAIL
exit signs/emergency lights/exit discharge lights passed. Fire extinguishers passed. Can not sign off until the fire lane, fire hydrant..ect items have been corrected.

Steve Phone #: ###-####
BLD17-02012 FIRE-Final Inspection5/29/20185/30/20185/30/2018 10:59:55 AMAFAIL
exit signs/emergency lights/exit discharge lights passed. Fire extinguishers passed. Can not sign off until the fire lane, fire hydrant..ect items have been corrected.


Steve Phone #: ###-####
BLD17-02016 FIRE-Final Inspection5/29/20185/30/20185/30/2018 10:54:56 AMAFAIL
Todays isnpection I verified the fire extinguishers, exit signs/emergency lights. The north end of the west corridor exit sign/emergency light/exit discharge light did not function as well as the corridor emergency light. Also the building can not be signed off untill the fire lane and fire hydrant issues have been addressed

Steve Phone #: ###-####
FIR18-00418 INSP-Final Inspection5/29/20185/30/20185/30/2018 10:18:55 AMAPASS
Permit finaled
FIR18-00107 INSP-Final Inspection5/29/20185/30/20185/30/2018 9:37:16 AMAPASS
Permit finaled


John will be there at 7:00am would like to start as soon as possible. Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00441 INSP-Final Inspection5/29/20185/30/20185/30/2018 9:36:50 AMAPASS
Permit finaled


John will be there at 7:00am would like to start as soon as possible. Phone #: ###-#### Inspection requested via web by Sam Ball
BLD18-00074 FIRE-Final Inspection5/29/20185/30/20185/30/2018 8:25:04 AMAPASS
Life safety passed. No sprinkler or alarm

George Dean will be the Super on site for the inspection. Inspection requested via web by Anne Motschull