Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01612 Final5/7/20195/7/20195/7/2019 3:38:44 PMPNR
Rob Phone #: ###-####
MEC19-01612 Rough-in5/7/20195/7/20195/7/2019 3:38:30 PMPFAIL
Rob Phone #: ###-#### - Need to seal exhaust duct. need access to roof, Need to install sleeves ob fire dampers that comply with the manufactures instructions, Need to install retaining angles per instructions on fire dampers after sheetrock is complete. need to install duct mounted access doors for fire dampers.
MEC16-03405 Mec-Aging Inspection5/7/20195/7/20195/7/2019 3:15:42 PM CANC
Called and spoke with homeowner. Work is still on going
MEC18-05917 Rough-in5/7/20195/7/20195/7/2019 3:14:29 PMPPASS
hardlid Phone #: ###-#### Inspection requested via web by Nicholas Paige - Okay to cover hard lids in rooms 431, 432, 433, 602, 603
MEC18-02721 Final5/6/20195/7/20195/7/2019 2:31:38 PMPPASS
Phone #: ###-#### Inspection requested via web by PATTY KIRK
MEC18-02722 Final5/6/20195/7/20195/7/2019 2:31:08 PMPPASS
Phone #: ###-#### Inspection requested via web by PATTY KIRK
MEC18-04599 Mec-Aging Inspection5/7/20195/7/20195/7/2019 10:24:51 AM DONE
Building permit was finaled without mechanical being signed off. House appears to be occupied at this time. I called contractor and asked them to get with homeowner to schedule final inspection
MEC19-01866 Final5/6/20195/7/20195/7/2019 10:21:00 AMAFAIL
Lock box 7420 Phone #: ###-#### Inspection requested via web by Bryan Palmer - Need to install co sensors, fuses in A/C disconnect are over sized. Need plumbing permit pulled for replacing fixtures.
MEC19-01765 Rough-in5/6/20195/7/20195/7/2019 9:53:39 AMAFAIL
should be ready for inspection. Phone #: ###-#### Inspection requested via web by Oleg Chervak - Need 8" fresh air to return plenum, 6" is installed. Need to see framing repaired above fireplace to verify clearances
MEC19-01887 Final5/7/20195/7/20195/7/2019 9:50:30 AMPCANC
Gas pressure test is all that is needed for this work. Phone #: ###-#### >> Inspection requested via web by Melissa Skinner Inspection cancelled from web by: Melissa Skinner
MEC18-04583 Mec-Aging Inspection5/7/20195/7/20195/7/2019 9:03:36 AM DONE
expired
MEC18-04583 DOC - Permit Expired5/7/20195/7/20195/7/2019 9:03:16 AMAPASS
No scheduled activity in the last 180 days. permit is expired
MEC19-01615 Final5/3/20195/7/20195/7/2019 12:00:00 AMACANC
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 11:15 AM . Contact for Right Now is Mary ###-####

Phone #: ###-#### >> Inspection requested via web by Mary LaFayette