Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00187 FIR-Aging Inspection5/8/20205/8/20205/11/2020 7:38:43 AM PASS
Permit has been finaled.
FIR13-00187 INSP-Final Inspection5/8/20205/8/20205/8/2020 3:16:48 PMPPASS
Permit finaled. Doors repaired.
FIR20-00172 INSP-Sprinkler Rough-in5/8/20205/8/20205/8/2020 1:11:31 PMPPASS
Rough-in passed. Piping can be covered.

Brian *screened* Phone #: ###-####
FIR19-00769 INSP-Final Inspection5/7/20205/8/20205/8/2020 1:09:27 PMAPASS
Permit finaled.

Please give Jim Lewis a call to schedule the inspection time. ###-#### Phone #: ###-#### Inspection requested via web by Joshua Hansen
BLD19-00413 FIRE-Final Inspection5/7/20205/8/20205/8/2020 11:31:37 AMAPASS
Life safety passed. Owner to remove exit sign over office door as discussed.

Mark Phone #: ###-####
BLD19-04891 FIRE-Final Inspection5/7/20205/8/20205/8/2020 11:30:55 AMAFAIL
Life safety will be ok to sign off when the project related fire alarm permit is finaled.

I would like to meet onsite to review any corrections if need be.

Thanks,
Dana McCarter
###-#### Phone #: ###-#### Inspection requested via web by Drew Moorhouse
FIR20-00103 INSP-Final Inspection5/7/20205/8/20205/8/2020 11:30:08 AMAFAIL
Need monitor modules installed and as-builts showing the installation of the monitor modules for the trouble signals from the dry pipe sprinkler system accelerators. Per tech they worked wednesday. This piece of equipment needs to be monitored per IFC 903.4. Also need the map updated showing all initiating devices. Need NFPA 72 Record of Completion.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten