FIR12-00610
| INSP-Sprinkler Rough-in | 5/8/2013 | 5/9/2013 | 5/9/2013 3:43:20 PM | A | PASS |
|
|
Hard lids ok to cover. I noed one location in the northwest corner of the building where upright sprinkler coverage is needed above one of the hardlids.
|
BLD12-02551
| FIRE-Final Inspection | 5/9/2013 | 5/9/2013 | 5/9/2013 3:15:34 PM | P | PASS |
|
|
life safety passed.
|
FIR13-00070
| INSP-Sprinkler Rough-in/Hydro | 5/8/2013 | 5/9/2013 | 5/9/2013 3:13:31 PM | A | PART |
|
|
The underground and dry system hydro tests passed. The wet system failed again. The previous correction items have been addressed.
|
FIR12-00549
| INSP-Final Inspection | 5/7/2013 | 5/9/2013 | 5/9/2013 3:09:43 PM | A | PASS |
|
|
Permit finaled. I need as-builts showing the added heat detector, new a/v and the interconnection to the existing door mags....ect.
|
FIR13-00207
| INSP-Sprinkler Rough-in | 5/8/2013 | 5/9/2013 | 5/9/2013 3:07:32 PM | A | PASS |
|
|
overhead cover inspection passed for the most part and the piping can be covered. The only issue is the 9' rule is being used off of two walls which is not allowed. Revised head spacing will be checked at final.
|
BLD13-01027
| FIRE-Final Inspection | 5/9/2013 | 5/9/2013 | 5/9/2013 3:05:46 PM | P | PASS |
|
|
Life safety passed
|
BLD12-02722
| FIRE-Final Inspection | 5/8/2013 | 5/9/2013 | 5/9/2013 10:11:39 AM | A | CANC |
|
|
Wrong permit number. Needed club house
|
FIR12-00033
| INSP-Final Inspection | 5/7/2013 | 5/9/2013 | 5/9/2013 8:47:20 AM | A | CANC |
|
|
need to start at 7am Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
|