BLD18-00266
| FIRE-Final Inspection | 6/19/2018 | 6/19/2018 | 6/19/2018 12:32:31 PM | P | FAIL |
|
|
Fire alarm modifications will be required for space, conference room has no notification, horn strobe next to area where wall was build for small break area will need to be relocated to provide correct coverage. Exit signs/emergency lighting will need to be serviced or replaced, fire extinguisher will need to have annual inspection performed and tagged with a current inspection tag.
Provide correct address (Permit says 121 9th St Suite 101, number above north exterior door is 915 Idaho).
Murray Phone #: ###-####
|
FIR17-00267
| INSP-Sprinkler Rough-in/Hydro | 6/18/2018 | 6/19/2018 | 6/19/2018 11:51:09 AM | A | DONE |
|
|
Hydrostatic test for level 3 witnessed, no pressure loss observed at riser provided gauge.
Contact Ken Orahood -###-#### 30 Min prior to Hydro Insp on 3rd Floor Start please.
thank YOU. Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00241
| INSP-Sprinkler Rough-in | 6/18/2018 | 6/19/2018 | 6/19/2018 11:03:01 AM | A | PART |
|
|
Rough to cover inspection for IBR (In Building Riser) complete, IBR approved for cover, remaining underground to be installed at a later date.
just for the IBR. Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR18-00159
| INSP-Sprinkler Rough-in | 6/18/2018 | 6/19/2018 | 6/19/2018 10:19:31 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping in rooms on levels 2, 3 and 4 complete, notated city approved drawings with red in areas approved for cover.
3rd and 4th floor Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
BLD18-01079
| FIRE-Final Inspection | 6/18/2018 | 6/19/2018 | 6/19/2018 9:41:59 AM | A | PASS |
|
|
No fire sprinklers, fire alarm inspection is complete (Fire alarm system is only in daycare section of building), fire extinguishers are in place with current inspection tags, knox box was being mounted at time of inspection and is located by the 3813 entrance. Final life fire safety nispection complete.
Dana Phone #: ###-####
|