MEC18-05844
| Final | 6/24/2019 | 6/25/2019 | 6/25/2019 3:55:24 PM | P | FAIL |
|
|
Mike - ###-#### Code:0555 Phone #: ###-#### Inspection requested via web by Bryan Palmer- need uv protection on mini split condenser outside- supply register doesnt fit in boot garage entry
|
MEC19-02715
| Final | 6/25/2019 | 6/25/2019 | 6/25/2019 3:37:11 PM | P | PASS |
|
|
Homeowner Jane Hepworth ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok
|
MEC19-02714
| Final | 6/25/2019 | 6/25/2019 | 6/25/2019 3:12:10 PM | P | PASS |
|
|
installer Travis ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok- 5lb flue test pass
|
MEC19-02557
| Final | 6/19/2019 | 6/25/2019 | 6/25/2019 2:37:34 PM | P | PASS |
|
|
Please inspect after 2:30 PM and call Frank Rendon prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- a/c coil co ok
|
MEC19-02160
| Rough-in | 6/25/2019 | 6/25/2019 | 6/25/2019 2:23:30 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey- R/I ok
|
MEC19-02160
| Pressure Test | 6/25/2019 | 6/25/2019 | 6/25/2019 2:23:14 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Aaron Toomey- 5lb flue pass- 20lb gas already passed
|
MEC19-02741
| Final | 6/25/2019 | 6/25/2019 | 6/25/2019 1:53:06 PM | P | PART |
|
|
###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello- need verification exhaust ducts are sealed to existing duct take picture and send to me- need verification that unit heater that fluing is not tied in is staying that way and gas valve and flex connector needs removed and plug off gas shut off valve- talked with GC he was going to talk tom owner on what to do
|
MEC19-02590
| Final | 6/25/2019 | 6/25/2019 | 6/25/2019 12:59:34 PM | P | FAIL |
|
|
The key is under the mat if no one is there. Ray Phone #: ###-#### Inspection requested via web by Ray Bolinger- need air balance report onsite- exhaust fan needs to be switched when all lights come on not just on over that station
|
MEC19-01950
| Final | 6/24/2019 | 6/25/2019 | 6/25/2019 12:27:48 PM | P | FAIL |
|
|
IMPORTANT: PLEASE CALL Brandon @ Lifeways to Schedule this inspection @ ###-#### Phone #: ###-#### Inspection requested via web by Holly Tarvin- 1- need to install 4 wet switches on secondary drains on coils 2- need uv protection on all lineset outside 3- need weather tight conduit whip between disconnect and a/cs 4 locations 4- 2 a/cs at entry need right size fuses installed in disconnects
recall in when corrections fixed walked job with maintenance personell
|
MEC18-03192
| Mec-Aging Inspection | 6/25/2019 | 6/25/2019 | 6/25/2019 7:45:30 AM | | CANC |
|
|
|
MEC18-03192
| DOC - Permit Expired | 6/25/2019 | 6/25/2019 | 6/25/2019 7:45:06 AM | A | PASS |
|
|
no calls
|