ELE18-00727
| Electrical Rough-In | 6/29/2018 | 6/29/2018 | 6/29/2018 2:26:25 PM | P | FAIL |
|
|
Ceiling cover. Thank you Phone #: ###-#### Inspection requested via web by Tom Jenkins BCC 4 05 17- It shall be unlawful to cover electrical wiring prior to inspection. Grid boarders remove and recall
|
ELE18-01691
| Permanent Service | 6/29/2018 | 6/29/2018 | 6/29/2018 1:05:25 PM | A | PASS |
|
|
Von Phone #: ###-#### Inspection requested via web by Sean DeLacy Available fault current posted inside panel door. 18,722 amps highest availble on 25k rated main. p/s u/g n ok
|
ELE17-03393
| Electrical Rough-In | 6/28/2018 | 6/29/2018 | 6/29/2018 10:37:05 AM | A | PART |
|
|
Contact: Caleb Burke Phone #: ###-#### Inspection requested via web by Deb Gooden Kitchen and day room rough in ok cover, Bathroom and captains quarters ok to 1-side only.
|
ELE18-02123
| Electrical Rough-In | 6/28/2018 | 6/29/2018 | 6/29/2018 9:29:03 AM | A | PASS |
|
|
Phone #: 2088595236 >> Inspection requested via mobile web by Rich Englert Detached garage rough in ok cover
|
ELE18-00352
| Final | 6/28/2018 | 6/29/2018 | 6/29/2018 8:59:58 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson Units locked, up entrance wet tile no access, garages locked. Recall when ready
|