Inspections for the day of: Friday, June 30, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03931 Electrical Rough-In6/30/20176/30/20176/30/2017 2:58:27 PMPPASS
units 501,502,504 thru 509, 521,522 Phone #: ###-#### Inspection requested via web by Cathy Duchek
704 and rooms noted signed off in office rough in ok cover
ELE16-03342 Final6/30/20176/30/20176/30/2017 1:48:27 PMPFAIL
Phone #: ###-#### Inspection requested via web by cris flores
110.3- Box noted in master shower is for equipmant to be mounted in shower, when asked for instructions for listing for wet locations contractor stated all power to box has been disconnected and he refused to install in location.
110.3- GFCI protection shall be provided as per manufacturers instructions for bath fan installed in shower.
210.52(C)- Area around nook built in table has counter space that shall have receptacle outlet adjacent to counter. 1 side exposed, need additional for left side if facing table.
314.16- Box mounted in pull out for receptacle shall be of sufficient size for wiring and device. 11.25 cubic inches minimum.
404.9- All face plates shall be installed to completely enclose boxes. switches in garage and misc else where.
422.16- Flexible cord for disposal shall be installed to verify length..
Class A GFCI protection for floor heat has been verified on thermostats.
Caution female owner being very difficult.
ELE17-01903 Rough-In Permanent Service6/30/20176/30/20176/30/2017 12:43:55 PMPPASS
Keys are on top of the service on the neighbors house to the right. Idaho power has to swap power. Phone #: ###-#### Inspection requested via web by Kendra Lanham
Duplicate request. Approved 6-19-17. All wiring fished in walls. Rough in ok cover p/s o/h rec ok
ELE17-01549 Electrical Rough-In6/29/20176/30/20176/30/2017 11:54:33 AMAPASS
Shane is the contact
cell #: ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates
General contractor asked all electrical inspections be noted on clip board in job trailer on east side.
Southern most flag pole rough in ok cover
ELE17-00938 Final6/30/20176/30/20176/30/2017 11:17:57 AMPPASS
Please call prior to inspection as electrician is not on site Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Final ok
ELE17-02075 Electrical Rough-In6/29/20176/30/20176/30/2017 10:34:29 AMAPASS
pool underground and bonding Phone #: ###-#### Inspection requested via web by Ryan Wake
Bonding 4 corners and water at bottom of north clean out. Underground and bonding rough in ok cover
ELE17-02068 Final6/29/20176/30/20176/30/2017 10:15:42 AMAPASS
Hot Tub Hook Up Phone #: ###-#### Inspection requested via web by Rowdy Monroe Final ok
ELE17-01937 Final6/30/20176/30/20176/30/2017 10:15:10 AMPPASS
Service change and feed to hot tub final ok
ELE17-02077 Electrical Rough-In6/29/20176/30/20176/30/2017 9:27:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Terry Scott
2nd receptacle for vanity basin stubbed out wall on right side. Master bath remodel rough in ok cover
MIS17-00204 ELE-Conference6/23/20176/30/20176/29/2017 11:11:11 AMADONE
Idaho Power conmplaint-
230.24- Overhead service entrance conductors shall clear a flat through 3/12 pitch roof by 8' or 4/12 and steeper roof by 3' minimum.
Electrical permit required for heater noted on BLD15-04178.
Owner doing job by himself and making efforts to provide safety for overhead service entrance conductors.