Inspections for the day of: Tuesday, July 18, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00610 FIR-Aging Inspection7/18/20177/18/20177/24/2017 9:11:18 AM NR
I spoke to Colton with SimplexGrinnell about status. He is going to follow up.
FIR13-00540 FIR-Aging Inspection7/18/20177/18/20177/24/2017 9:11:00 AM NR
I spoke to Colton with SimplexGrinnell about status. He is going to follow up.
BLD17-02127 FIRE-Final Inspection7/18/20177/18/20177/18/2017 2:35:07 PMPPASS
life safety passed.


Jim Phone #: ###-####
FIR17-00302 INSP-Sprinkler Rough-in7/18/20177/18/20177/18/2017 11:27:41 AMAPART
Underground supply piping is ok to cover but as-builts are required showing the multiple offsets required due to the power transformer.
FIR17-00372 INSP-Final Inspection7/17/20177/18/20177/18/2017 11:24:32 AMPFAIL
No testing performed. Need strobe coverage modified for the entire space including short corridor and restroom. As-builts to both plan review and myself is ok.
BLD15-02010 FIRE-Final Inspection7/17/20177/18/20177/18/2017 11:16:41 AMAFAIL
Provide address, repair the exit discharge light, remove the thumbturn lock from the exit door (keyed,sticker,indicator ok), resubmit plans showing the revised wall layout and get plan review approval for non-ADA hardware and threshold height.
BLD17-02385 FIRE-Final Inspection7/17/20177/18/20177/18/2017 10:08:01 AMAFAIL
Porvide annual inspection for the fire sprinkler system, provide annual inspection for the fire extinguishers, repair and provide inspection for the fire alarm system, provide missing exit signs, provide emergency lighting through out common areas/classrooms, repair the non-functional exit signs/emergency lights.
FIR16-00738 INSP-Sprinkler Rough-in7/17/20177/18/20177/18/2017 9:04:50 AMAPASS
The remaining sprinkler piping can be covered. The remaining tenting passed. There are a few can lights that are close to the new pendant sprinklers that I will need verification on.
BLD16-03864 FIRE-Final Inspection7/17/20177/18/20177/18/2017 8:27:17 AMAPASS
Life safety passed. Sticker was not installed yet but will be before building inspection.
BLD17-01360 FIRE-Final Inspection7/17/20177/18/20177/18/2017 8:12:21 AMAPASS
life safety passed
BLD17-01329 FIRE-Final Inspection7/17/20177/18/20177/18/2017 12:00:00 AMPCANC
CANC Per Jeff; parts not coming in. call half hour to meet // jeff Phone #: ###-####