FIR13-00610
| FIR-Aging Inspection | 7/18/2017 | 7/18/2017 | 7/24/2017 9:11:18 AM | | NR |
|
|
I spoke to Colton with SimplexGrinnell about status. He is going to follow up.
|
FIR13-00540
| FIR-Aging Inspection | 7/18/2017 | 7/18/2017 | 7/24/2017 9:11:00 AM | | NR |
|
|
I spoke to Colton with SimplexGrinnell about status. He is going to follow up.
|
BLD17-02127
| FIRE-Final Inspection | 7/18/2017 | 7/18/2017 | 7/18/2017 2:35:07 PM | P | PASS |
|
|
life safety passed.
Jim Phone #: ###-####
|
FIR17-00302
| INSP-Sprinkler Rough-in | 7/18/2017 | 7/18/2017 | 7/18/2017 11:27:41 AM | A | PART |
|
|
Underground supply piping is ok to cover but as-builts are required showing the multiple offsets required due to the power transformer.
|
FIR17-00372
| INSP-Final Inspection | 7/17/2017 | 7/18/2017 | 7/18/2017 11:24:32 AM | P | FAIL |
|
|
No testing performed. Need strobe coverage modified for the entire space including short corridor and restroom. As-builts to both plan review and myself is ok.
|
BLD15-02010
| FIRE-Final Inspection | 7/17/2017 | 7/18/2017 | 7/18/2017 11:16:41 AM | A | FAIL |
|
|
Provide address, repair the exit discharge light, remove the thumbturn lock from the exit door (keyed,sticker,indicator ok), resubmit plans showing the revised wall layout and get plan review approval for non-ADA hardware and threshold height.
|
BLD17-02385
| FIRE-Final Inspection | 7/17/2017 | 7/18/2017 | 7/18/2017 10:08:01 AM | A | FAIL |
|
|
Porvide annual inspection for the fire sprinkler system, provide annual inspection for the fire extinguishers, repair and provide inspection for the fire alarm system, provide missing exit signs, provide emergency lighting through out common areas/classrooms, repair the non-functional exit signs/emergency lights.
|
FIR16-00738
| INSP-Sprinkler Rough-in | 7/17/2017 | 7/18/2017 | 7/18/2017 9:04:50 AM | A | PASS |
|
|
The remaining sprinkler piping can be covered. The remaining tenting passed. There are a few can lights that are close to the new pendant sprinklers that I will need verification on.
|
BLD16-03864
| FIRE-Final Inspection | 7/17/2017 | 7/18/2017 | 7/18/2017 8:27:17 AM | A | PASS |
|
|
Life safety passed. Sticker was not installed yet but will be before building inspection.
|
BLD17-01360
| FIRE-Final Inspection | 7/17/2017 | 7/18/2017 | 7/18/2017 8:12:21 AM | A | PASS |
|
|
life safety passed
|
BLD17-01329
| FIRE-Final Inspection | 7/17/2017 | 7/18/2017 | 7/18/2017 12:00:00 AM | P | CANC |
|
|
CANC Per Jeff; parts not coming in. call half hour to meet // jeff Phone #: ###-####
|