BLD19-01549
| FIRE-Final Inspection | 7/20/2020 | 7/20/2020 | 7/21/2020 7:13:22 AM | P | CANC |
|
|
Could no perform on site inspectio due to covid protocols so requested a video of the smoke alarms functioning by 4:00pm. Did not receive anything by 7:00am the following morning so inspection is canceled. WIll need to be rescheduled. photo ok // Joe Phone #: ###-#### or ###-#### Jack (manager)
|
BLD19-00527
| FIRE-Conference | 7/17/2020 | 7/20/2020 | 7/20/2020 3:20:49 PM | P | DONE |
|
|
I went over life safety requirements to begin the building sign offs. The biggerst issue is the need to submit to Joe Bruce temp fire dept access plans for approval.
Phone #: ###-#### Inspection requested via web by Lee Scott
|
FIR20-00313
| INSP-Sprinkler Rough-in | 7/20/2020 | 7/20/2020 | 7/20/2020 2:52:03 PM | P | PASS |
|
|
The tenting passed for the two west most third floor apartments. Piping is ok to cover.
Matt - screened Phone #: ###-####
|
FIR20-00462
| INSP-Final Inspection | 7/20/2020 | 7/20/2020 | 7/20/2020 1:54:38 PM | P | PASS |
|
|
Permit finaled.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD19-00250
| FIRE-Final Inspection | 7/20/2020 | 7/20/2020 | 7/20/2020 12:59:27 PM | P | PART |
|
|
Life safety passed for apartments 115,119,210,213,214,215,217,218,219,231,232 Phone #: ###-####
|
BLD20-01650
| FIRE-Final Inspection | 7/17/2020 | 7/20/2020 | 7/20/2020 11:05:23 AM | A | FAIL |
|
|
The existing fire alarm system, notification, needs to be extended into the new room at the Restroom in the Kitchen Area.
screened // Isaac Phone #: ###-####
|
NAF20-00038
| INSP-Final | 7/20/2020 | 7/20/2020 | 7/20/2020 10:59:04 AM | P | FAIL |
|
|
I spoke to Kim about the need for plans to match (wall has been removed), fire sprinkler pendant modified since two of them are too close together since wall was removed, need ceiling tile re-installed, need single action hardware installed on the infill door.
Call for access Phone #: 7607515050 >> Inspection requested via mobile web by Kim
|