MEC19-03217
| Final | 7/24/2019 | 7/24/2019 | 7/24/2019 3:54:11 PM | P | PASS |
|
|
Please call Maddie on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- a/c coil in attic co ok
|
MEC19-03191
| Final | 7/24/2019 | 7/24/2019 | 7/24/2019 3:21:05 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok- need to insulate r/a plenum to r-6 in garage
|
MEC19-03071
| Final | 7/24/2019 | 7/24/2019 | 7/24/2019 2:56:18 PM | P | CANC |
|
|
Please Call Kim 30 min prior to arrival so she can make sure she is home. Phone number is ###-#### Phone #: ###-#### Inspection requested via web by Ashley Shoecraft
|
MEC19-03229
| Pressure Test | 7/24/2019 | 7/24/2019 | 7/24/2019 2:56:06 PM | P | FAIL |
|
|
Contact Kim prior to arrival Phone #: ###-#### Inspection requested via web by Jamee Shoecraft- 20lb gas pass to fireplace- 20lb gas fail to range at 4 psi- need bbq line installed and pressure tested too
|
MEC19-02661
| Pressure Test | 7/24/2019 | 7/24/2019 | 7/24/2019 2:30:59 PM | P | FAIL |
|
|
Jeremy Phone #: ###-####- gauge wont zero out
|
MEC19-03078
| Rough-in | 7/23/2019 | 7/24/2019 | 7/24/2019 2:20:00 PM | P | PASS |
|
|
Darus Phone #: ###-####- R/I on 2 supply ducts ok
|
MEC19-03078
| Final | 7/24/2019 | 7/24/2019 | 7/24/2019 2:19:10 PM | P | PASS |
|
|
Darus Phone #: ###-####
|
MEC19-03082
| Final | 7/23/2019 | 7/24/2019 | 7/24/2019 1:45:13 PM | P | PASS |
|
|
Husband works nights, come after 1pm if possible. Thank you! Phone #: ###-#### Inspection requested via web by Julie McMillan- a/c coil co ok
|
MEC19-02944
| Final | 7/23/2019 | 7/24/2019 | 7/24/2019 1:20:23 PM | P | CANC |
|
|
INSPECTION FOR FURNACE/AC CHANGE OUT.
No one lives in the home. The homeowner''''s sister can come let you in. Please call her 30-60 minutes before inspection so she can let you in. Karen Hendrix, ###-#### Phone #: ###-#### Inspection requested via web by John Eastman- i rescheduled this for tomorrow am per phone call with tenant
|
MEC19-03192
| Pressure Test | 7/24/2019 | 7/24/2019 | 7/24/2019 1:15:16 PM | P | PASS |
|
|
Gauge is outside Phone #: ###-#### Inspection requested via web by Mary LaFayette- 20lb gas pass- need to seal gas penetration where enters into crawl by final and co detectors installed in there is none- recall in when ready
|
MEC19-02961
| Rough-in | 7/24/2019 | 7/24/2019 | 7/24/2019 12:58:43 PM | P | FAIL |
|
|
Up-flow system - ducting in attic... Phone #: ###-#### Inspection requested via web by Bruce Lacy- need nail plates on dryer duct at ceiling both sides- exhaust fans need installed and hooked up- need inert tape on gas line penetration at meter location- need approved man j onsite for inspection- need nail plate on lineset at ceiling- left correction notice front window
|
MEC19-02961
| Pressure Test | 7/24/2019 | 7/24/2019 | 7/24/2019 12:56:16 PM | P | PASS |
|
|
Up-flow system - ducting in attic... Phone #: ###-#### Inspection requested via web by Bruce Lacy- 20lb gas pass
|
MEC19-01751
| Final | 7/24/2019 | 7/24/2019 | 7/24/2019 12:41:28 PM | P | FAIL |
|
|
Builder should have floor registers in.. they or on site Phone #: ###-#### Inspection requested via web by Bruce Lacy- need uv protection on arma flex outside and extend arma flex bare copper showing- need 3/4" 90 degree on pvc condensate drain outside- need to seal both outside penetrations weather tight- need air balance performed and report onsite
|
MEC19-03173
| Final | 7/23/2019 | 7/24/2019 | 7/24/2019 12:24:35 PM | P | PASS |
|
|
Please call Barron abut 30 minutes prior to inspection so he can get home from work to meet you. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
|
MEC19-03028
| Final | 7/17/2019 | 7/24/2019 | 7/24/2019 11:52:14 AM | P | CANC |
|
|
Tenant is Kendra ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- i rescheduled this for friday pm per conversation with tenant
|
MEC19-03028
| Final | 7/24/2019 | 7/24/2019 | 7/24/2019 11:51:33 AM | P | CANC |
|
|
by 200pm- ###-####- rescheduled for friday pm
|
MIS19-00214
| MEC-Conference | 7/24/2019 | 7/24/2019 | 7/24/2019 11:36:25 AM | P | NH |
|
|
work w/o permit; wrong connector used on MT type wire Phone #: ###-####- left correction notice front door to pull mechanical permit for A/C installed
|
MEC19-00741
| Rough-in | 7/23/2019 | 7/24/2019 | 7/24/2019 11:19:10 AM | A | PASS |
|
|
Please call Brad at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum- R/I ok- ok for ceiling tiles- need air balance report for mau and class 1 hood at final and all equipment set into working place under class 1 hood
|
MEC19-03192
| Pressure Test | 7/24/2019 | 7/24/2019 | 7/24/2019 10:45:30 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette
|
MEC19-03021
| Rough-in | 7/23/2019 | 7/24/2019 | 7/24/2019 10:34:05 AM | A | PASS |
|
|
Vinnie ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace R/I ok
|
MEC19-03216
| Final | 7/23/2019 | 7/24/2019 | 7/24/2019 10:08:14 AM | A | PASS |
|
|
Shane Phone #: ###-#### Inspection requested via web by Brandon Sorensen- final ok- all work per approved drawings onsite- signed card
|
MEC19-02812
| Rough-in | 7/23/2019 | 7/24/2019 | 7/24/2019 9:37:21 AM | A | FAIL |
|
|
Crawl is complete Phone #: ###-#### Inspection requested via web by Bob Ferrin- ducting in crawl needs to maintain 4" off ground- insultion on wye branches is coming off and exposed fiberglass showing- some ducts are pinched between main supply and joist- recall in when corrections are made
|
MEC19-03054
| Rough-in | 7/23/2019 | 7/24/2019 | 7/24/2019 9:21:59 AM | A | PASS |
|
|
Gari ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace R/I ok
|
MEC19-03211
| Pressure Test | 7/23/2019 | 7/24/2019 | 7/24/2019 9:16:43 AM | A | PART |
|
|
Please inspect under ground gasline Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass underground only- ok to backfill
|
MEC19-01925
| Final | 7/23/2019 | 7/24/2019 | 7/24/2019 9:00:25 AM | A | PASS |
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- final ok- seal on ducts and transfer ok- ok for ceiling tiles-
|
MEC19-03146
| Rough-in | 7/23/2019 | 7/24/2019 | 7/24/2019 8:46:26 AM | A | PASS |
|
|
Light test on remaining welds so we can cover with fire wrap. Phone #: ###-#### Inspection requested via web by Drew Tverdy- light test on all grease duct ok- ok for firewrap 1st and 2nd layers
|
MEC18-05886
| Mec-Aging Inspection | 7/24/2019 | 7/24/2019 | 7/24/2019 7:47:15 AM | | FAIL |
|
|
homeowner needs to call in inspection if work has been done- will need to request extension if no activity
|
MEC18-04218
| Mec-Aging Inspection | 7/24/2019 | 7/24/2019 | 7/24/2019 7:45:15 AM | | CANC |
|
|
|
MEC18-04218
| DOC - Permit Expired | 7/24/2019 | 7/24/2019 | 7/24/2019 7:45:06 AM | A | PASS |
|
|
no activity
|