Inspections for the day of: Wednesday, July 25, 2018.
Number of inspections: 31
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDan Ediger
TitlePLM-INSPECTOR
Phone #869-5166
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM18-03146 Final7/24/20187/25/20187/26/2018 10:51:00 AMPPASS
PLEASE CONTACT SKYLER ###-#### WITH ANY QUESTIONS OR CONCERNS. Phone #: ###-#### Inspection requested via web by Ben Davis
PLM18-03018 Plumbing Rough-in7/24/20187/25/20187/25/2018 4:55:01 PMPPART
Carmeron Phone #: ###-####.
Install a fitting to roll the wye off the center lin on the wc
PLM18-03129 Water and/or Sewer7/24/20187/25/20187/25/2018 4:31:28 PMPPART
Sewer only. 2 sewer services, one new and one existing. Darrel Carter is onsite contact Phone #: ###-#### Inspection requested via web by Mike Basabe.
Sewer off of the gym is appoved.
The grease intercepter is set needs 24hr test and vented. Vent by plumber per excavator.
PLM17-04364 Final7/25/20187/25/20187/25/2018 4:06:01 PMPPASS
Charles Phone #: ###-####
PLM17-04364 DOC - Permit Finaled7/25/20187/25/20187/25/2018 4:05:45 PMPPASS
PLM18-03095 Water and/or Sewer7/25/20187/25/20187/25/2018 4:05:18 PMPPASS
Jaun Phone #: ###-####
PLM18-03124 Water and/or Sewer7/25/20187/25/20187/25/2018 3:50:47 PMPPASS
PLM18-03124 DOC - Permit Finaled7/25/20187/25/20187/25/2018 3:50:37 PMPPASS
PLM18-03121 Sprinkler (Final)7/25/20187/25/20187/25/2018 3:11:29 PMPPASS
Dave Phone #: ###-####
PLM17-04243 Plumbing Rough-in7/25/20187/25/20187/25/2018 2:42:12 PMPPASS
PLM17-04252 Plumbing Rough-in7/25/20187/25/20187/25/2018 2:20:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Brian Johansen
PLM17-04251 Plumbing Rough-in7/25/20187/25/20187/25/2018 2:20:39 PMPPASS
Phone #: ###-#### Inspection requested via web by Brian Johansen
PLM17-03254 Plumbing Rough-in7/25/20187/25/20187/25/2018 2:20:22 PMPCANC
Phone #: ###-#### Inspection requested via web by Brian Johansen. Already passed r-in
PLM18-03128 Final7/25/20187/25/20187/25/2018 2:02:25 PMPPASS
Homeowner Ken Baumgartner ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
PLM18-02878 Plumbing Rough-in7/24/20187/25/20187/25/2018 12:40:12 PMAPASS
Phone #: ###-#### Inspection requested via web by Nicholas Paige. New water line to an added coffee maker outlet.
PLM18-02415 Plumbing Rough-in7/24/20187/25/20187/25/2018 12:17:41 PMANR
Ready to test Phone #: ###-#### Inspection requested via web by Robert Frazier
PLM18-03061 Water and/or Sewer7/24/20187/25/20187/25/2018 12:16:59 PMAPART
Alex Phone #: ###-####.
Pressure test before covering joints.
Run tracer wire to all three units.
PLM18-03060 Water and/or Sewer7/24/20187/25/20187/25/2018 12:16:05 PMAPART
Alex Phone #: ###-####.
Run the tracer wire to each unit and pressure test lines before covering the joints
PLM18-03059 Water and/or Sewer7/24/20187/25/20187/25/2018 12:15:08 PMAPART
Alex Phone #: ###-####.
Ok to caver all but the joints.
A prrssure test is required befire the joints are covered.
run the tracer wire continuous to each unit.
PLM18-03014 Final7/19/20187/25/20187/25/2018 11:57:11 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette
PLM18-02939 Water and/or Sewer7/24/20187/25/20187/25/2018 11:36:39 AMAPART
Pressure test on building water supply Phone #: ###-#### Inspection requested via web by MICHAEL BYERS. The water service is ok to cover
PLM18-03144 Water and/or Sewer7/24/20187/25/20187/25/2018 11:18:20 AMACANC
Phone #: ###-#### Inspection requested via web by Raul Castanon. passed as a groundwork
PLM18-03144 Groundwork7/25/20187/25/20187/25/2018 11:17:57 AMAPASS
Phone #: ###-#### Inspection requested via web by Raul Castanon. 4" trunk line and water service stub-out.
PLM18-03105 Water and/or Sewer7/25/20187/25/20187/25/2018 11:16:54 AMPPART
Jim Phone #: ###-####. Sewer ok to cover
PLM18-02313 Storm Drains7/24/20187/25/20187/25/2018 10:44:31 AMAPASS
Alfredo Phone #: ###-####
PLM18-02313 DOC - Permit Finaled7/25/20187/25/20187/25/2018 10:44:20 AMPPASS
24 hr test complete. storm drain and sewer test complete
PLM18-02320 Groundwork7/24/20187/25/20187/25/2018 10:43:03 AMAPASS
Sanitary Underground Inspection. If questions call Jerry @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
PLM18-03124 Water and/or Sewer7/24/20187/25/20187/25/2018 10:25:30 AMAPART
Dale Phone #: ###-####. first 100 feet
PLM17-04142 PLM-Aging Inspection7/25/20187/25/20187/25/2018 8:44:07 AM PASS
contractor to schedule
PLM17-04141 PLM-Aging Inspection7/25/20187/25/20187/25/2018 8:42:32 AM PASS
contractor to schedule
PLM17-01174 PLM-Aging Inspection7/25/20187/25/20187/25/2018 8:29:40 AM NR
wip