Inspections for the day of: Friday, August 11, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00392 INSP-Conference8/11/20178/11/20178/11/2017 2:36:08 PMPDONE
Per my conversation with Scott Arellano, additional manual pull stations will not be required.
FIR17-00236 INSP-Final Inspection8/11/20178/11/20178/11/2017 2:10:54 PMPPASS
Permit finaled
FIR17-00426 INSP-Final Inspection8/11/20178/11/20178/11/2017 1:27:12 PMPFAIL
As-builts are needed showing all of the audio/visual devices and the accurate location of all devices. Coverage needs to be modified in two corridors and coverage provided in the other half of the Conference Room.
BLD17-01278 FIRE-Final Inspection8/11/20178/11/20178/11/2017 1:08:57 PMPFAIL
Need the project related fire alarm permit finaled. Need to repair the two exit signs and provide two exit signs in the Break Room. Need panic hardware installed in Break Room. Need additional emergency lighting in the Open Office area. Need fire extinguishers provided.
BLD17-01397 FIRE-Final Inspection8/11/20178/11/20178/11/2017 1:07:15 PMPPASS
Life safety passed
BLD17-02603 FIRE-Final Inspection8/9/20178/11/20178/11/2017 11:20:43 AMAPASS
Life safety passed
FIR17-00365 INSP-Sprinkler Rough-in8/10/20178/11/20178/11/2017 9:28:04 AMAPASS
The piping for the remote FDC has the tape installed and can be covered.
NAF17-00023 INSP-Final8/9/20178/11/20178/11/2017 9:27:34 AMAFAIL
Repair the retaining straps, provide the calc sticker and provide the updated approved drawings for the earthquake bracing locations
NAF17-00050 INSP-Sprinkler Rough-in/Hydro8/9/20178/11/20178/11/2017 9:26:35 AMAFAIL
Provide block off plate for the outlet at FACP, provide testing of the duct smoke detectors, provide one bell that functions correctly at the FDC

Call prior to going Phone #: 8418763 >> Inspection requested via mobile web by Matt
BLD17-01371 FIRE-Final Inspection8/10/20178/11/20178/11/2017 7:56:13 AMAPART
Phase B (North East Quadrant) life safety is passed. Will need the door mag request to exit buttons modified

temp occ // Jason Phone #: ###-####