Inspections for the day of: Tuesday, August 22, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02738 Final8/22/20178/22/20178/22/2017 1:59:52 PMPPASS
Please call Nick Harris at ###-#### to meet in Lobby, for access to escort you into the Ada County Jail. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
Installed 100 amp 480 volt feed to transformer and panel to new server. Security all low volt beyond this point.
Final ok
ELE16-01667 Final8/22/20178/22/20178/22/2017 11:24:55 AMAPART
Unit 106 and Finish 105 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Rooms noted TCO ok
ELE17-02179 Final8/21/20178/22/20178/22/2017 10:58:04 AMANH
if not call Dylan ###-####. Thank You have a good day. Phone #: ###-#### Inspection requested via web by daniel bibikov
House occupied no answer at door. Must have someone here when occupied. Called contractor must recall.
ELE17-01860 Final8/21/20178/22/20178/22/2017 10:57:39 AMANH
Phone #: ###-#### Inspection requested via web by daniel bibikov
House occupied no answer at door. Must have someone here when occupied. Called contractor must recall.
ELE17-02733 Electrical Rough-In8/21/20178/22/20178/22/2017 10:42:19 AMAFAIL
Call John if any issues. Thanks. Phone #: ###-#### Inspection requested via web by John Harvey
210.52(A)- Dn bed all walls 24" or wider shall have a receptacle outlet installed.
300.4- Where NM cable is run thru bored or notched holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates.
334.30- NM cable shall be supported at intervals not to exceed 4 1/2' and be secured with in 12" of a box. Back can and kitchen boxes.
ELE17-01951 Electrical Rough-In8/21/20178/22/20178/22/2017 9:49:58 AMAPASS
Underground cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Checked junction boxes, all conduits have bushed ends. Underground S. E. headed west rough in ok cover
ELE17-01549 Electrical Rough-In8/21/20178/22/20178/22/2017 8:25:15 AMAPASS
Pouring at 7:30am - Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
Contractor sent pics of install, informed an in person inspection required for future pours to check all listings and installations. Told to inform General ample time shall be given to complete. Off pics provided rough in ok cover