Inspections for the day of: Tuesday, August 27, 2013.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-01487 FIRE-Final Inspection8/27/20138/27/20138/27/2013 3:59:58 PMPPART
Lube Bay and Car Wash life safety complete. The fire door between the Lube Bay and the existing shop area shall remain locked until door has been tested and passed. As of now there are no "links" for activation installed on both sides of the wall at the roof deck as required in NFPA 80.
BLD13-02201 FIRE-Final Inspection8/20/20138/27/20138/27/2013 3:41:40 PMPPASS
Life safety passed
FIR13-00268 INSP-Final Inspection8/26/20138/27/20138/27/2013 3:39:42 PMPCANC
Overbooked. I spoke to ray about rescheduling. Phone #: ###-####
FIR12-00490 INSP-Final Inspection8/26/20138/27/20138/27/2013 3:07:16 PMPPASS
Permit finaled
FIR12-00610 INSP-Sprinkler Rough-in/Hydro8/27/20138/27/20138/27/2013 2:37:07 PMPFAIL
Overhead hydro test failed due to visible pressure loss on the guage.
BLD13-01583 FIRE-Final Inspection8/26/20138/27/20138/27/2013 1:48:23 PMAPASS
Life safety passed.
BLD13-02004 FIRE-Final Inspection8/26/20138/27/20138/27/2013 1:09:09 PMAFAIL
Repair the exit signs as marked on the plans. Provide annual inspection for the fire exitinguishers. Lower the fire extinguisher in the south east corner of the ware house so as not to exceed 5' AFF.
FIR12-00380 FIR-Aging Inspection8/27/20138/27/20138/27/2013 12:31:00 PM NR
work is in progress
FIR13-00341 INSP-Sprinkler Rough-in/Hydro8/26/20138/27/20138/27/2013 9:57:27 AMAPASS
Inspection was for a cover of the underground piping. Piping can be covered. 2" poly like the others.
FIR13-00320 INSP-Final Inspection8/26/20138/27/20138/27/2013 9:37:56 AMAFAIL
Alot of ceiling tile is missing and needs to be installed prior to a final sign off.
BLD13-01743 FIRE-Final Inspection8/26/20138/27/20138/27/2013 9:30:28 AMAPASS
Life safety passed
FIR13-00356 INSP-Final Inspection8/26/20138/27/20138/27/2013 9:29:17 AMAPASS
permit finaled
FIR13-00356 INSP-Sprinkler Rough-in8/26/20138/27/20138/27/2013 9:28:14 AMAPASS
rough-in passed.
FIR13-00250 INSP-Sprinkler Rough-in/Hydro8/26/20138/27/20138/27/2013 12:00:00 AMPDONE
Underground hydro passed