BLD16-02899
| FIRE-Final Inspection | 8/31/2017 | 9/1/2017 | 9/1/2017 3:08:18 PM | A | CANC |
|
|
Herb Phone #: ###-####
|
FIR16-00738
| INSP-Final Inspection | 8/31/2017 | 9/1/2017 | 9/1/2017 3:01:32 PM | A | FAIL |
|
|
The interconnection with the fire alarm panel needs to be retested due to wrong signals from tamper and pressure switches. Also need the forward flush test for 13psi out of the 2 1/2" drain. Need test papers as well
Adam Phone #: ###-####
|
FIR14-00701
| INSP-Final Inspection | 9/1/2017 | 9/1/2017 | 9/1/2017 2:45:09 PM | P | CANC |
|
|
John Phone #: ###-####
|
BLD17-01354
| FIRE-Final Inspection | 8/31/2017 | 9/1/2017 | 9/1/2017 2:08:09 PM | A | FAIL |
|
|
Life safety will be ok to pass when the project related fire alarm pemit has been finaled
|
FIR16-00284
| INSP-Sprinkler Rough-in | 8/31/2017 | 9/1/2017 | 9/1/2017 2:07:31 PM | A | PART |
|
|
Todays walk through was for the first floor apartments. I noted one painted concealer pendant head and on pendant that is blocked by a surface mounted light.
|
NAF17-00028
| INSP-Final | 9/1/2017 | 9/1/2017 | 9/1/2017 11:47:46 AM | A | DONE |
|
|
Permit finaled per Scott this has been review under the sprinkler design
|
NAF17-00020
| INSP-Final | 9/1/2017 | 9/1/2017 | 9/1/2017 11:47:10 AM | A | DONE |
|
|
permit finaled
|
FIR17-00261
| INSP-Sprinkler Rough-in | 8/31/2017 | 9/1/2017 | 9/1/2017 11:16:41 AM | A | PART |
|
|
Sprinkler heads outside of new corridor system are ok to cover. One pendant needs to be added in the Storage Room as per plans.
|
FIR16-00821
| INSP-Sprinkler Rough-in | 8/31/2017 | 9/1/2017 | 9/1/2017 10:19:06 AM | A | PART |
|
|
See the city approved plans for locations clouded where the sprinkler piping rough-in passed. Hat channel can be installed but piping can not be covered until draft stop/compartments can be verified for the CC2 heads.
|
FIR17-00472
| INSP-Final Inspection | 8/31/2017 | 9/1/2017 | 9/1/2017 9:42:26 AM | A | PASS |
|
|
Permit finaled.
|
FIR17-00040
| INSP-Final Inspection | 8/31/2017 | 9/1/2017 | 9/1/2017 9:41:39 AM | A | FAIL |
|
|
Todays inspection was just a partial. Installed head end equipment tested ok, manual pull statons tested ok, hood suppression system tested ok. The sprinkler system interconnections have problems as the tamper switches and pressure switches report as a/c power loss. All notification devices tested ok and are sync'd. Need to re-verify the fire sprinkler interconnects, duct detectors, fire door release, security door release, smoke detectors and heat detectors. I verified off site monitoring for the devices tested. Address was ok. Will need as-builts showing the minimal changes.
|