ELE17-03003
| Electrical Rough-In | 9/11/2017 | 9/11/2017 | 9/11/2017 3:58:06 PM | P | PASS |
|
|
Wall cover Phone #: ###-#### Inspection requested via web by cris flores Phase 1 consists of buffing rms, sanding rms at east end of building. Wall rough in ok cover
|
ELE17-02992
| Permanent Service | 9/8/2017 | 9/11/2017 | 9/11/2017 3:24:12 PM | P | FAIL |
|
|
Please call ahead to meet on site - Victor Phone #: ###-#### Service Unsafe- 250.52- Permanent service shall have grounding electrode system containing 2 ground rods. 300.15- All terminations shall be in a box. Old feed to house still present and exposed to contact. 240.6- #12 conductors tap off 60 amp feed, 20 amp max required. Insulation has peeled off #12 conductors where exposed to sunlight. * Owner wants to use service on pole for power to build new house on lot. Told to remove all load wiring and install a GFCI protected receptacle outlet on pole for construction. Shop feeders also have illegal tap with bare expose wiring present.
|
ELE17-02884
| Conference | 8/30/2017 | 9/11/2017 | 9/11/2017 2:20:29 PM | P | DONE |
|
|
Dalton ###-#### Discussed code requirements for service change. Underground water pipe is PVC, 2 ground rods 6' min apart and also bond for plumbing pipe at water heater, bonding if metal nipple used. Max height of breaker handles, owner bought 3/0 THWN, multi wire branch circuit arangement, de-ox for aluminum terminations. Identification of grounded conductor.
|
ELE17-02575
| Final | 9/11/2017 | 9/11/2017 | 9/11/2017 1:31:44 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by mark hood 210.8- All devices providing GFCI protection shall be located in a readily accessible location. 300.15- A box shall be installed at all splice points. Flood light located on house garage soffit hanging on wires without a box at time of inspection. BCC 4-05-32- Code violations not to be retained. 406.9(B)(1)- All 15 and 20 amp 120 volt receptacle outlets located in a wet location shall be (WR) weather resistant type.
|
ELE17-02099
| Electrical Rough-In | 9/11/2017 | 9/11/2017 | 9/11/2017 12:52:27 PM | P | PASS |
|
|
Harlan Phone #: ###-#### Underground from house to garage rough in ok cover
|
ELE17-02780
| Electrical Rough-In | 9/11/2017 | 9/11/2017 | 9/11/2017 11:31:58 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mark M Central area as noted on contractor print wall rough in ok cover
|
ELE17-01549
| Electrical Rough-In | 9/8/2017 | 9/11/2017 | 9/11/2017 10:52:54 AM | A | PASS |
|
|
Linear lights. Area in front of vestibule. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Area noted 2 lights in front of vestibule rough in ok cover
|
ELE17-02631
| Final | 9/9/2017 | 9/11/2017 | 9/11/2017 10:12:47 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Thomas wilson Final ok
|
ELE17-02867
| Rough-In Permanent Service | 9/11/2017 | 9/11/2017 | 9/11/2017 9:47:11 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|
ELE17-02265
| Final | 9/11/2017 | 9/11/2017 | 9/11/2017 9:38:12 AM | A | PASS |
|
|
code 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE17-02866
| Rough-In Permanent Service | 9/11/2017 | 9/11/2017 | 9/11/2017 9:10:49 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|
ELE17-02264
| Final | 9/11/2017 | 9/11/2017 | 9/11/2017 8:56:53 AM | A | PASS |
|
|
code 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|