Inspections for the day of: Monday, September 11, 2017.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03003 Electrical Rough-In9/11/20179/11/20179/11/2017 3:58:06 PMPPASS
Wall cover Phone #: ###-#### Inspection requested via web by cris flores
Phase 1 consists of buffing rms, sanding rms at east end of building. Wall rough in ok cover
ELE17-02992 Permanent Service9/8/20179/11/20179/11/2017 3:24:12 PMPFAIL
Please call ahead to meet on site - Victor Phone #: ###-####
Service Unsafe-
250.52- Permanent service shall have grounding electrode system containing 2 ground rods.
300.15- All terminations shall be in a box. Old feed to house still present and exposed to contact.
240.6- #12 conductors tap off 60 amp feed, 20 amp max required. Insulation has peeled off #12 conductors where exposed to sunlight.
* Owner wants to use service on pole for power to build new house on lot. Told to remove all load wiring and install a GFCI protected receptacle outlet on pole for construction.
Shop feeders also have illegal tap with bare expose wiring present.
ELE17-02884 Conference8/30/20179/11/20179/11/2017 2:20:29 PMPDONE
Dalton ###-####
Discussed code requirements for service change. Underground water pipe is PVC, 2 ground rods 6' min apart and also bond for plumbing pipe at water heater, bonding if metal nipple used. Max height of breaker handles, owner bought 3/0 THWN, multi wire branch circuit arangement, de-ox for aluminum terminations. Identification of grounded conductor.
ELE17-02575 Final9/11/20179/11/20179/11/2017 1:31:44 PMPFAIL
Phone #: ###-#### Inspection requested via web by mark hood
210.8- All devices providing GFCI protection shall be located in a readily accessible location.
300.15- A box shall be installed at all splice points. Flood light located on house garage soffit hanging on wires without a box at time of inspection.
BCC 4-05-32- Code violations not to be retained.
406.9(B)(1)- All 15 and 20 amp 120 volt receptacle outlets located in a wet location shall be (WR) weather resistant type.
ELE17-02099 Electrical Rough-In9/11/20179/11/20179/11/2017 12:52:27 PMPPASS
Harlan Phone #: ###-####
Underground from house to garage rough in ok cover
ELE17-02780 Electrical Rough-In9/11/20179/11/20179/11/2017 11:31:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Mark M
Central area as noted on contractor print wall rough in ok cover
ELE17-01549 Electrical Rough-In9/8/20179/11/20179/11/2017 10:52:54 AMAPASS
Linear lights. Area in front of vestibule. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
Area noted 2 lights in front of vestibule rough in ok cover
ELE17-02631 Final9/9/20179/11/20179/11/2017 10:12:47 AMAPASS
Phone #: ###-#### Inspection requested via web by Thomas wilson
Final ok
ELE17-02867 Rough-In Permanent Service9/11/20179/11/20179/11/2017 9:47:11 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok
ELE17-02265 Final9/11/20179/11/20179/11/2017 9:38:12 AMAPASS
code 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok
ELE17-02866 Rough-In Permanent Service9/11/20179/11/20179/11/2017 9:10:49 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok
ELE17-02264 Final9/11/20179/11/20179/11/2017 8:56:53 AMAPASS
code 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok