BLD11-01097
| FIRE-Conference | 9/13/2011 | 9/13/2011 | 9/13/2011 3:24:24 PM | P | DONE |
|
|
Levi and I went over emergency light placement
|
FIR11-00362
| INSP-Final Inspection | 9/12/2011 | 9/13/2011 | 9/13/2011 3:05:36 PM | P | FAIL |
|
|
The hood suppression system operated correctly. But all of the correct sign off paper work had not been provided and the appliance layout for the large hood did not match the paper work.
|
FIR11-00349
| INSP-Final Inspection | 9/12/2011 | 9/13/2011 | 9/13/2011 3:03:23 PM | P | FAIL |
|
|
The hood suppression system operated correctly. But all of the correct sign off paper work had not been provided and the appliance layout for the large hood did not match the paper work.
|
FIR11-00242
| INSP-Sprinkler Rough-in/Hydro | 9/13/2011 | 9/13/2011 | 9/13/2011 3:00:02 PM | P | FAIL |
|
|
Above ground hydro test failed
|
FIR11-00419
| INSP-Alarm Testing | 9/12/2011 | 9/13/2011 | 9/13/2011 2:47:41 PM | P | PASS |
|
|
permit finaled
|
FIR11-00497
| INSP-Final Inspection | 9/13/2011 | 9/13/2011 | 9/13/2011 1:17:50 PM | P | FAIL |
|
|
I left a voice mail for Nate with Shilo. I also went to the job site but the doors were locked. No inspection performed.
|
BLD11-01175
| FIRE-Conference | 9/12/2011 | 9/13/2011 | 9/13/2011 11:36:54 AM | A | DONE |
|
|
I spoke to Steve Hill and Josh about the fire protection requirements for this project. I agreed to let them continue to cover if adequate access is provided to all areas needing inspection from the interior of the soffits or from the roof. This access is required to verify sprinkler installation or the installation of non-combustible insulation when they are installed.
|
BLD11-02128
| FIRE-Final Inspection | 9/12/2011 | 9/13/2011 | 9/13/2011 11:24:35 AM | A | PASS |
|
|
life safety passed
|
FIR11-00423
| INSP-Sprinkler Rough-in | 9/12/2011 | 9/13/2011 | 9/13/2011 11:00:28 AM | A | PASS |
|
|
Piping can be covered but access will need to be provided to verify that the hanger was repaired. Also the pendant head near the rear exit needs to be relocated closer to the edge of the soffit as discussed. This can be verified at the final.
|
FIR10-00527
| INSP-Final Inspection | 9/13/2011 | 9/13/2011 | 9/13/2011 10:57:31 AM | P | PASS |
|
|
permit finaled
|
BLD11-02085
| FIRE-Final Inspection | 9/12/2011 | 9/13/2011 | 9/13/2011 10:54:09 AM | A | PASS |
|
|
life safety passed
|
FIR10-00527
| INSP-Alarm Testing | 9/12/2011 | 9/13/2011 | 9/13/2011 9:22:53 AM | A | DONE |
|
|
Testing is done. Wrong inspection type called in.
|
BLD11-01683
| FIRE-Final Inspection | 9/12/2011 | 9/13/2011 | 9/13/2011 9:21:04 AM | A | CANC |
|
|
Need the project related fire alarm permit finaled.
|
FIR11-00391
| INSP-Final Inspection | 9/13/2011 | 9/13/2011 | 9/13/2011 9:20:39 AM | A | PASS |
|
|
Permit finaled
|
FIR11-00430
| INSP-Final Inspection | 9/12/2011 | 9/13/2011 | 9/13/2011 9:20:12 AM | A | FAIL |
|
|
Could not get the hvac unit to turn on. It actually started to smoke from the return intake. No testing was able to be performed. Re-inspection fee applied.
|
BLD11-01981
| FIRE-Final Inspection | 9/12/2011 | 9/13/2011 | 9/13/2011 9:18:39 AM | A | FAIL |
|
|
Provide suite number, provide access to the fire sprinkler riser room to verify annual inspection and fire alarm system, provide annual inspection for the fire extinguisher.
|
BLD11-00781
| FIRE-Final Inspection | 9/12/2011 | 9/13/2011 | 9/13/2011 8:30:12 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Chris Palmer Inspection cancelled from web by: Chris Palmer
|