FIR13-00359
| INSP-Sprinkler Rough-in | 9/24/2013 | 9/24/2013 | 9/25/2013 3:41:53 PM | P | PASS |
|
|
Tenting has been corrected and piping can be covered.
|
BLD13-01288
| FIRE-Sprinkler Rough-in | 9/24/2013 | 9/24/2013 | 9/25/2013 2:29:13 PM | P | PASS |
|
|
Tenting has been corrected. Sprinkler piping can be covered.
|
FIR13-00512
| INSP-Sprinkler Rough-in | 9/24/2013 | 9/24/2013 | 9/24/2013 3:39:27 PM | P | PASS |
|
|
Sprinkler piping is ok to cover.
|
BLD12-02415
| FIRE-Final Inspection | 9/23/2013 | 9/24/2013 | 9/24/2013 1:10:09 PM | A | FAIL |
|
|
This was just a conference for today. I noted that both smoke detectors at the door are not centered and one exceeds 5' from the door. Unable to test the exit signs and emergency lights due to patients. All other items appear ok. Bob Phone #: ###-####
|
BLD13-01020
| FIRE-Final Inspection | 9/23/2013 | 9/24/2013 | 9/24/2013 10:16:06 AM | A | FAIL |
|
|
Remove the keyed lock/dead bolt from the beer cooler or provide single action hardware on the inside. Finish installing the duct smoke detectors and relocate as discussed to be in the center of the air flow and able to mount flush. Install the remote annunciators and provide testing and immediate shutdown as discussed. All other items for the "Store" area appear ok.
|
FIR13-00359
| INSP-Sprinkler Rough-in | 9/23/2013 | 9/24/2013 | 9/24/2013 9:56:30 AM | A | FAIL |
|
|
Tenting still is not repaired. Piping can not be covered.
|