BLD11-02288
| FIRE-Final Inspection | 9/26/2011 | 9/26/2011 | 9/26/2011 3:42:46 PM | P | FAIL |
|
|
Provide exit signs with battery backup in locations as marked on the plans, provide "Door to remain unlocked when building is occupied" sticker at the main exit door, provide single action hardware on the west front exit door and all of the other exterior exit doors and remove the deadbolts, provide missing covers for the electrical outlets and breaker boxes in the remote warehouse, provide 2A, 10BC fire extinguishers as discussed with current inspection tags and resubmit plans for the remote warehouse that matches the installed floor plan.
|
FIR11-00297
| INSP-Final Inspection | 9/26/2011 | 9/26/2011 | 9/26/2011 3:38:54 PM | P | FAIL |
|
|
Plan modifications need to be submitted due to door magnet installation and one line diagram not matching installation. The relays that are shown to activate the AES are actually releasing the doors. No testing was performed.
|
FIR11-00399
| INSP-Final Inspection | 9/26/2011 | 9/26/2011 | 9/26/2011 3:36:54 PM | P | FAIL |
|
|
Did not perform the testing due to the intella tap not being installed on the AES dialer.
|
FIR11-00474
| INSP-Sprinkler Rough-in | 9/26/2011 | 9/26/2011 | 9/26/2011 1:53:54 PM | P | PASS |
|
|
Four additional heads as marked on the plans are ok for cover.
|
BLD11-02061
| FIRE-Final Inspection | 9/23/2011 | 9/26/2011 | 9/26/2011 11:33:54 AM | A | PASS |
|
|
life safety passed
|