Inspections for the day of: Thursday, September 27, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02411 Electrical Rough-In9/27/20189/27/20189/27/2018 3:22:49 PMPPASS
Stairwells and 2 Floor 2 Units.
Contact Scott Wilson
Thank you Phone #: ###-#### Inspection requested via web by Tom Betty
2nd floor units and stairwells ok to cover
ELE18-02273 Final9/27/20189/27/20189/27/2018 2:55:41 PMPFAIL
Phone #: ###-#### Inspection requested via web by Jason Wicks
GFCI protection required for island outlet
Protect romex behind drawer in island
ELE18-03572 Permanent Service9/27/20189/27/20189/27/2018 2:47:51 PMPPASS
p/s u/g n ok
ELE18-03572 Electrical Rough-In9/27/20189/27/20189/27/2018 2:47:27 PMPPASS
Phone #: ###-#### Inspection requested via web by Nick Larson

Rough in ok to cover
ELE18-03577 Final9/26/20189/27/20189/27/2018 12:51:29 PMPFAIL
Pls contact Brad (Foreman) @ ###-#### or Preston (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes
Type NM cable shall not be ran in wet locations
ELE18-03718 Conference9/27/20189/27/20189/27/2018 12:36:52 PMPFAIL
Inspection requested via web by Matthew Whit
Discussed waht areas as needed to be brought up to code. All contractors works on will be current code related
ELE18-02537 Final9/26/20189/27/20189/27/2018 11:37:28 AMAPASS
unit 126, check in at front desk Phone #: ###-#### Inspection requested via web by David Nelson
Final ok
ELE18-03659 Permanent Service9/26/20189/27/20189/27/2018 10:27:27 AMAPASS
Joe Kaminsky is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
p/s o/h n ok
ELE18-03605 Final9/26/20189/27/20189/27/2018 9:16:26 AMAPASS
Phone #: ###-#### Inspection requested via web by Patrick Paz
Final ok