BLD12-00382
| FIRE-Final Inspection | 9/4/2013 | 9/4/2013 | 9/6/2013 7:06:06 AM | P | DONE |
|
|
Mike and I discussed the requirement for the exit discharge lighting for the north exits of the showroom area.
|
FIR12-00648
| INSP-Final Inspection | 9/3/2013 | 9/4/2013 | 9/4/2013 4:19:10 PM | P | PASS |
|
|
permit finaled
|
FIR12-00610
| INSP-Final Inspection | 9/3/2013 | 9/4/2013 | 9/4/2013 4:18:18 PM | P | PASS |
|
|
Permit finaled
|
BLD13-02340
| FIRE-Final Inspection | 9/4/2013 | 9/4/2013 | 9/4/2013 4:17:32 PM | P | FAIL |
|
|
Remove thumb turn locks from all marked required exits, provide sticker at the main exit, resubmitt plans showing the preferred exiting, provide exit signs and emergency lights as discussed or per the resubmittted plans, provide fire extinguishers as discussed, provide single action hardware on exterior doors eccept for the main exit.
|
BLD12-03333
| FIRE-Final Inspection | 9/4/2013 | 9/4/2013 | 9/4/2013 4:11:24 PM | P | PASS |
|
|
life safety passed. The sliding door hardware is not ADA compliant and will need to be corrected prior to the building final.
|
FIR13-00448
| INSP-Final Inspection | 9/4/2013 | 9/4/2013 | 9/4/2013 2:35:58 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00113
| INSP-Final Inspection | 8/28/2013 | 9/4/2013 | 9/4/2013 10:05:26 AM | A | FAIL |
|
|
New duct smoke detectors are listed to be mounted outside as per Joe with System Sensor. But duct smoke detectors were not wired up for power. Inspection stopped and will need to be resceduled.
|