FIR12-00737
| FIR-Aging Inspection | 9/8/2015 | 9/8/2015 | 9/9/2015 10:34:41 AM | | NR |
|
|
Jeff is going to follow up.
|
FIR12-00474
| FIR-Aging Inspection | 9/8/2015 | 9/8/2015 | 9/9/2015 8:54:29 AM | | NR |
|
|
Jeff is going to follow up.
|
FIR15-00335
| INSP-Supply line flush | 9/4/2015 | 9/8/2015 | 9/8/2015 3:00:33 PM | P | PART |
|
|
Underground flush failed due to no water. Underground hydro passed.
|
FIR15-00082
| INSP-Sprinkler Rough-in/Hydro | 9/8/2015 | 9/8/2015 | 9/8/2015 1:09:25 PM | P | PASS |
|
|
Overhead hydro test and rough to cover of the third floor passed. Piping can be covered.
|
BLD15-01425
| FIRE-Final Inspection | 9/5/2015 | 9/8/2015 | 9/8/2015 9:23:15 AM | A | PASS |
|
|
Fire/Safety passed
|
FIR15-00562
| INSP-Final Inspection | 9/4/2015 | 9/8/2015 | 9/8/2015 8:15:22 AM | A | FAIL |
|
|
See the city approved plans for devices tested. I noted four areas in the POD/cells where the wall mounted 110cd strobes are overspaced.
|
BLD15-02511
| FIRE-Final Inspection | 9/4/2015 | 9/8/2015 | 9/8/2015 8:14:00 AM | A | PASS |
|
|
Life safety passed
|