Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00737 FIR-Aging Inspection9/8/20159/8/20159/9/2015 10:34:41 AM NR
Jeff is going to follow up.
FIR12-00474 FIR-Aging Inspection9/8/20159/8/20159/9/2015 8:54:29 AM NR
Jeff is going to follow up.
FIR15-00335 INSP-Supply line flush9/4/20159/8/20159/8/2015 3:00:33 PMPPART
Underground flush failed due to no water. Underground hydro passed.
FIR15-00082 INSP-Sprinkler Rough-in/Hydro9/8/20159/8/20159/8/2015 1:09:25 PMPPASS
Overhead hydro test and rough to cover of the third floor passed. Piping can be covered.
BLD15-01425 FIRE-Final Inspection9/5/20159/8/20159/8/2015 9:23:15 AMAPASS
Fire/Safety passed
FIR15-00562 INSP-Final Inspection9/4/20159/8/20159/8/2015 8:15:22 AMAFAIL
See the city approved plans for devices tested. I noted four areas in the POD/cells where the wall mounted 110cd strobes are overspaced.
BLD15-02511 FIRE-Final Inspection9/4/20159/8/20159/8/2015 8:14:00 AMAPASS
Life safety passed