Inspections for the day of: Friday, September 9, 2016.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00439 INSP-Sprinkler Rough-in9/9/20169/9/20169/9/2016 1:34:57 PMPCANC
Per contact project is not ready for inspection today. Phone #: ###-#### Inspection requested via web by Connie Danes
BLD16-02335 FIRE-Final Inspection9/8/20169/9/20169/9/2016 1:33:03 PMAFAIL
No approved plans or small documents on site. I noted the possible need for code compliant hardware on both exit doors from the DIning Area and exit discharge lights at the same two exits. I deferred this decision to the plan reviewer. David Phone #: ###-####
BLD16-03217 FIRE-Final Inspection9/7/20169/9/20169/9/2016 12:23:03 PMPFAIL
Replace painted sprinkler heads, repaire exit signs and emergency lights, reverse door swing on rear exit screen door, provide lever hardware on the door to second exit and provide occupant load sign (162)
BLD16-00142 FIRE-Final Inspection9/8/20169/9/20169/9/2016 12:17:46 PMAFAIL
Provide racking permit for storage racks over 8'-0", All storage to remain under 12'-0" (6'-0") or a high pile permit is required, Provide exit sign on second floor, Repair all exit signs and emregency lights, Provide sprinkler protection under the new door and platform.
BLD14-03071 FIRE-Final Inspection9/8/20169/9/20169/9/2016 11:22:35 AMAPART
Life safety passed for units 107,108,207,208,307,308
BLD16-00275 FIRE-Final Inspection9/8/20169/9/20169/9/2016 8:06:55 AMAFAIL
Provide fire extinguishers as discussed for both levels, remove deadbolts from the restroom doors and provide single action hardware or get building code official approval.
BLD16-03277 BLD-Conference9/9/20169/9/20169/9/2016 12:00:00 AMPDONE
*Fire Conference* Troy Cobbley performed courtesy field inspection. Noted items: 1) Building fire alarm system in trouble condition; 2) Non functioning exit signs and emergency lights; Portable fire extinguishers nearly expired, recommend servicing. Permit not issued, no approved plans onsite. Correction items communicated to Jill (business owner).